6.117
Date Code 20171021
Instruction Manual
SEL-421 Relay
Protection Applications Examples
EHV Parallel 230 kV Underground Cables Example
k0M
Forward Zones ZSC Factor Magnitude (0.000–10)
6.105
k0A
Forward Zones ZSC Factor Angle (–180.0 to +180
degrees)
44.5
k0MR
Reverse Zones ZSC Factor Magnitude (0.000–10)
6.105
k0AR
Reverse Zones ZSC Factor Angle
(–180.0 to +180 degrees)
44.5
Ground-Distance Element Time Delay (Group)
Z1GD
Zone 1 Time Delay (OFF, 0.000–16000 cycles)
OFF
Z2GD
Zone 2 Time Delay (OFF, 0.000–16000 cycles)
OFF
Z3GD
Zone 3 Time Delay (OFF, 0.000–16000 cycles)
OFF
Distance Element Common Time Delay (Group)
Z1D
Zone 1 Time Delay (OFF, 0.000–16000 cycles)
0.000
Z2D
Zone 2 Time Delay (OFF, 0.000–16000 cycles)
20.000
Z3D
Zone 3 Time Delay (OFF, 0.000–16000 cycles)
0.000
SOTF Scheme (Group)
ESPSTF
Single-Pole Switch-Onto-Fault (Y, N)
N
EVRST
Switch-Onto-Fault Voltage Reset (Y, N)
Y
VRSTPU
Switch-Onto-Fault Reset Voltage (0.60–1.00 pu)
0.60–1.00 pu
52AEND
52A Pole Open Time Delay
(OFF, 0.000–16000 cycles)
OFF
CLOEND
CLSMON or Single Pole Open Delay
(OFF, 0.000–16000 cycles)
10.000
SOTFD
Switch-Onto-Fault Enable Duration
(0.500–16000 cycles)
10.000
CLSMON
Close Signal Monitor (SEL
OGIC
Equation)
IN102
Phase Instantaneous Overcurrent Pickup (Group)
50P1P
Level 1 Pickup (OFF, 0.25–100 A secondary)
9.57
Phase Overcurrent Definite-Time Delay (Group)
67P1D
Level 1 Time Delay (0.000–16000 cycles)
0.000
Phase Overcurrent Torque Control (Group)
67P1TC
Level 1 Torque Control (SEL
OGIC
Equation)
1
Negative-Sequence Instantaneous Overcurrent Pickup (Group)
50Q1P
Level 1 Pickup (OFF, 0.25–100 A secondary)
OFF
50Q2P
Level 2 Pickup (OFF, 0.25–100 A secondary)
0.60
50Q3P
Level 3 Pickup (OFF, 0.25–100 A secondary)
0.40
Negative-Sequence Overcurrent Definite-Time Delay (Group)
67Q2D
Level 2 Time Delay (0.000–16000 cycles)
0.000
67Q3D
Level 3 Time Delay (0.000–16000 cycles)
0.000
Negative-Sequence Overcurrent Torque Control (Group)
67Q2TC
Level 2 Torque Control (SEL
OGIC
Equation)
32GF
67Q3TC
Level 3 Torque Control (SEL
OGIC
Equation)
32GR
Table 6.31
Settings for 230 kV Parallel Cables Example (Sheet 3 of 5)
Setting
Prompt
Entry
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...