9.5
Date Code 20171021
Instruction Manual
SEL-421 Relay
ASCII Command Reference
Description of Commands
MET E
Use the
MET E
command to view the energy import and export quantities.
The reset command,
MET RE
, resets the Line, BK1, and BK2 energy metering
quantities. When you issue the
MET RE
command, the relay responds with
Reset Energy Metering (Y/N)
? If you answer
Y <Enter>
, the relay responds
with
Energy Metering Reset
.
MET RMS
Use the
MET RMS
command to view root-mean-square (rms) metering quanti-
ties. The relay includes power system harmonics and subharmonics in rms quan-
tities.
NOTE:
In firmware R310 and newer,
the rms value is zero when the current
is below 0.02 • I
NOM
.
MET SYN
Use the
MET SYN
command to view the synchronism-check reference voltage,
normalized source voltages, angles, and slip calculations.
If you have not enabled the synchronism-check function, the relay responds with
Synchronism Check Element Is Not Available
. (Enable synchronism check
with the Global settings E25BK1, E25BK2, and NUMBK; see
).
Table 9.3
MET E Command
Command
Description
Access Level
MET E
Display Line energy metering data.
1, B, P, A, O, 2
MET E
k
Display Line energy metering data successively for
k
times.
1, B, P, A, O, 2
MET RE
Reset Line energy metering data.
P, A, O, 2
Table 9.4
MET RMS Command
Command
a
a
Parameter
n
is 1 or 2 to indicate Circuit Breaker 1 or Circuit Breaker 2.
Description
Access Level
MET RMS
Display Line rms metering data.
1, B, P, A, O, 2
MET RMS
k
Display Line rms metering data successively for
k
times.
1, B, P, A, O, 2
MET BK
n
RMS
Display Circuit Breaker
n
rms metering data.
1, B, P, A, O, 2
MET BK
n
RMS
k
Display Circuit Breaker
n
rms metering data succes-
sively for
k
times.
1, B, P, A, O, 2
Table 9.5
MET SYN Command
Command
Description
Access Level
MET SYN
Display the synchronism-check values.
1, B, P, A, O, 2
MET SYN
k
Display the synchronism-check values successively
for
k
times.
1, B, P, A, O, 2
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...