Instruction Manual
SEL-421 Relay
Protection Applications Examples
500 kV Parallel Transmission Lines With Mutual Coupling Example
Ground-Distance Elements (21MG and 21XG)
Mho Ground-Distance Element Reach
Employ each zone of distance protection as follows:
➤
Zone 1—Instantaneous underreaching direct tripping
➤
Zone 2—Forward-looking tripping elements for the POTT scheme
and backup tripping
➤
Zone 3—Current reversal guard for the POTT scheme, echo tripping,
and weak infeed logic
Zone 1 Mho Ground-Distance Element Reach
Zone 1 mho ground-distance reach must meet the same requirement as that for
Zone 1 mho phase-distance protection; the reach setting should be no greater than
80 percent of the line.
Z1MG = 0.8 • Z
1L1
= 3.18
Z1MG :=
3.18
.
Zone 1 (OFF, 0.05–64
secondary)
Zone 2 Mho Ground-Distance Element Reach
Zone 2 mho and ground-distance reach must meet the same requirement as that
for Zone 2 mho phase-distance protection; the reach setting is 120 percent of the
line.
Z2MG = 1.2 • Z1L1 = 4.78
Z2MG :=
4.78
.
Zone 2 (OFF, 0.05–64
secondary)
Zone 3 Mho Ground-Distance Element Reach
Zone 3 mho ground-distance reach must meet the same requirement as that for
Zone 3 mho phase-distance protection; it equals the Zone 2 reach.
Z3MG = Z2MG = 4.78
Z3MG :=
4.78
.
Zone 3 (OFF, 0.05–64
secondary)
Quadrilateral Ground-Distance Element Reach
The reactive reach for each zone of quadrilateral ground-distance protection lies
on the relay characteristic angle (Z1ANG), rather than on the ordinate (reactance)
of the impedance plane (see
).
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...