4.11
Date Code 20171006
Instruction Manual
SEL-400 Series Relays
Front-Panel Operations
Front-Panel Layout
Use the following syntax to display the given Relay Word bit with the given alias.
If the Relay Word bit is asserted (logical 1), the LCD displays the set string in the
place of the value. If the Relay Word bit is deasserted (logical 0), the LCD dis-
plays the clear string in the place of the value. One or all of Alias, Set String, or
Clear String can be empty. If Alias is empty, then the LCD displays only the Set
or Clear Strings. If either Set String or Clear String is empty, then an empty line
is displayed when the bit matches that state. The text size determines if the dis-
play will be in single font or double font. If the text size is empty, the display will
be in single font.
DPxx :=
Name, “Alias”, “Set String”, “Clear String”, “Text Size”
Use the following syntax to display the given analog quantity with the given text
and formatting. Formatting must be in the form Width.Decimal,Scale with the
value of Name, scaled by “Scale,” formatted with total width “Width” and “Deci-
mal” decimal places. The width value includes the decimal point and sign charac-
ter, if applicable. The “scale” value is optional; if omitted, the scale factor is
processed as 1. If the numeric value is smaller than the field size requested, the
field is padded with spaces to the left of the number. If the numeric value will not
fit within the field width given, “$” characters are displayed. The text size deter-
mines if the display will be in single font or double font. If the text size is empty,
the display will be in single font.
DPxx :=
Name, “(Text1 Width.Decimal,Scale) Text2”, “Text Size”
Table 4.3
Display Point Settings—Boolean
Description
Range
Relay Word Bit Name
See the relay-specific instruction manual for a list of Relay
Word bits available in that relay.
Alias
ASCII string
Set String
ASCII string
Clear String
ASCII string
Text Size
S, D
Table 4.4
Display Point Settings—Analog
Description
Range
Analog Quantity Name
See the relay-specific instruction manual for a list of avail-
able analog quantities
“User Text and Formatting”
ASCII string
Text Size
S, D
Table 4.5
Display Point Settings—Boolean and Analog Examples (Sheet 1 of 2)
Example Display Point Setting Value
Example Display
IN101
IN101=1
IN101=0
MWHAIN,“{7.2}”
1234.56
50P1,Overcurrent,,
Overcurrent=1
Overcurrent=0
PSV01,Control,On,Off
Control=On
Control=Off
PSV02,Breaker,Tripped,
Breaker=Tripped
Empty Line
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...