6.85
Date Code 20171021
Instruction Manual
SEL-421 Relay
Protection Applications Examples
345 kV Tapped Overhead Transmission Line Example
CLOEND
CLSMON or Single Pole Open Delay (OFF, 0.000–16000 cycles)
10.000
SOTFD
Switch-Onto-Fault Enable Duration (0.500–16000 cycles)
10.000
CLSMON
Close Signal Monitor (SEL
OGIC
Equation)
IN102
Load Encroachment (Group)
ZLF
Forward Load Impedance (0.05–64
secondary)
12.50
ZLR
Reverse Load Impedance (0.05–64
secondary)
12.50
PLAF
Forward Load Positive Angle (–90.0 to +90 degrees)
45.0
NLAF
Forward Load Negative Angle (–90.0 to +90 degrees)
–45.0
PLAR
Reverse Load Positive Angle (+90.0 to +270 degrees)
135.0
NLAR
Reverse Load Negative Angle (+90.0 to +270 degrees)
225.0
Phase Instantaneous Overcurrent Pickup (Group)
50P1P
Level 1 Pickup (OFF, 0.25–100 A secondary)
49.80
Phase Overcurrent Definite-Time Delay (Group)
67P1D
Level 1 Time Delay (0.000–16000 cycles)
0.000
Phase Overcurrent Torque Control (Group)
67P1TC
Level 1 Torque Control (SEL
OGIC
Equation)
1
Residual Ground Instantaneous Overcurrent Pickup (Group)
50G1P
Level 1 Pickup (OFF, 0.25–100 A secondary)
OFF
50G2P
Level 2 Pickup (OFF, 0.25–100 A secondary)
1.00
50G3P
Level 3 Pickup (OFF, 0.25–100 A secondary)
0.50
Residual Ground Overcurrent Definite-Time Delay (Group)
67G2D
Level 2 Time Delay (0.000–16000 cycles)
0.000
67G3D
Level 3 Time Delay (0.000–16000 cycles)
0.000
Residual Ground Overcurrent Torque Control (Group)
67G2TC
Level 2 Torque Control (SEL
OGIC
Equation)
32GF
67G3TC
Level 3 Torque Control (SEL
OGIC
Equation)
32GR
Selectable Operating Quantity Inverse-Time Overcurrent Element 1 (Group)
51S1O
51S1 Operating Quantity (IA
n
, IB
n
, IC
n
, IMAX
n
, I1L, 3I2L, 3I0
n
)
a
3I0L
51S1P
51S1 Overcurrent Pickup (0.25–16 A secondary)
0.96
51S1C
51S1 Inverse Time Overcurrent Curve (U1–U5)
U3
51S1TD
51S1 Inverse Time Overcurrent Time Dial (0.50–15.00)
2.0
51S1RS
51S1 Inverse Time Overcurrent Electromagnetic Reset (Y, N)
Y
51S1TC
51S1 Torque Control (SEL
OGIC
Equation)
32GF
Zone/Level Direction (Group)
DIR3
Zone/Level 3 Directional Control (F, R)
R
Directional Control (Group)
ORDER
Ground Directional Element Priority (combine Q, V, I)
QV
E32IV
Zero-Sequence Voltage And Current Enable (SEL
OGIC
Equation)
1
Table 6.21
Settings for 345 kV Tapped TX Example (Sheet 3 of 4)
Setting
Prompt
Entry
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...