16.27
Date Code 20171006
Instruction Manual
SEL-400 Series Relays
DNP3 Communication
DNP3 Serial Application Example
Table 16.11
DNP3 Application Example Data Map
Label
Object
Custom
Map Index
Description
EN
1, 2
0
Relay enabled
TRIPLED
1, 2
1
Circuit Breaker tripped
IN101
1, 2
2
Relay Discrete Input 1
IN102
1, 2
3
Relay Discrete Input 2
IN103
1, 2
4
Relay Discrete Input 3
IN104
1, 2
5
Relay Discrete Input 4
SALARM
1, 2
6
Relay software alarm
HALARM
1, 2
7
Relay hardware alarm
TESTDB2
1, 2
8
Test mode enabled
RB01
10, 12
0
Remote Bit 1
RB02
10, 12
1
Remote Bit 2
RB03
10, 12
2
Remote Bit 3
RB04
10, 12
3
Remote Bit 4
RB05
10, 12
4
Remote Bit 5
RB06
10, 12
5
Remote Bit 6
OC1:CC1
10, 12
6
Circuit Breaker 1 trip/close pair
LIAFM
30, 32
0
IA magnitude
LIAFA
30, 32
1
IA angle
LIBFM
a
a
Assume the largest expected current is 2000 A and scale the analog value by a factor of 10 to
provide a resolution of 0.1 A and a maximum current of 3276.7 A. Report change events on a
change of 5 A.
30, 32
2
IB magnitude
LIBFA
b
b
Angles are scaled to 1/100 of a degree. Report change events on a change of 2 degrees.
30, 32
3
IB angle
LICFM
30, 32
4
IC magnitude
LICFA
30, 32
5
IC angle
VAFM
c
c
For a nominal voltage of 230 kV, scale the analog value by a factor of 100 to provide a resolution
of 10 V and a maximum value of 327.67 kV. Report 1 kV for change event reporting.
30, 32
6
VAY magnitude
VAFA
30, 32
7
VAY angle
VBFM
30, 32
8
VBY magnitude
VBFA
30, 32
9
VBY angle
VCFM
30, 32
10
VCY magnitude
VCFA
30, 32
11
VCY angle
3P_F
d
d
For a maximum load of 800 MW (or 800 mVar), scale the power by a factor of 40 to provide a
resolution of 0.025 MW and a maximum value of 819.175 MW. Report 1 MW for change event
reporting.
30, 32
12
Three-phase real power in MW
3Q_F
30, 32
13
Three-phase reactive power in MVAR
DC1
e
e
VDC1 is scaled by a factor of 1/100 of a volt. Report change events on a change of 2 V.
30, 32
14
DC1 voltage multiplied by 100
ACTGRP
40
0
Active settings group
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...