Settings
Group Settings
Make
through
settings if Group settings E79 := Y or Y1 or
EMANCL := Y. The number of settings also depends on the Global settings
NUMBK := 1 or 2, BK1TYP := 1 or 3, and BK2TYP := 1 or 3.
ALTS2
Alternative Synchronism Source 2 (SEL
OGIC
Equation)
NA
ASYNCS2 Alternative Synchronism Source 2 (VAY, VBY, VCY,
VAZ, VBZ, VCZ)
VCZ
AKS2M
Alternative Synchronism Source 2 Ratio Factor (0.10–3) 1.00
0.01
AKS2A
Alternative Synchronism Source 2 Angle Shift (0, 30,
60, 90, 120, 150, 180, 210, 240, 270, 300, 330 degrees)
0
30
25SFBK2
Maximum Slip Frequency—BK2 (OFF, 0.005–0.5 Hz)
0.050
0.001
ANG1BK2 Maximum Angle Difference 1—BK2 (3.0–80 degrees)
10.0
0.1
ANG2BK2 Maximum Angle Difference 2—BK2 (3.0–80 degrees)
10.0
0.1
TCLSBK2
Breaker 2 Close Time (1.00–30 cycles)
a
8.00
0.25
BSYNBK2 Block Synchronism Check—BK2 (SEL
OGIC
Equation)
NA
a
Adjust setting TCLSBK2 in 0.25-cycle steps.
Table 8.74
Recloser and Manual Closing
a
(Sheet 1 of 2)
Setting
Prompt
Default
Value
Increment
NSPSHOT Number of Single-Pole Reclosures (N, 1, 2)
N
ESPR1
Single-Pole Reclose Enable—BK1
(SEL
OGIC
Equation)
NA
ESPR2
Single-Pole Reclose Enable—BK2
(SEL
OGIC
Equation)
NA
N3PSHOT
Number of Three-Pole Reclosures (N, 1–4)
2
E3PR1
Three-Pole Reclose Enable—BK1
(SEL
OGIC
Equation)
PLT06
E3PR2
Three-Pole Reclose Enable—BK2
(SEL
OGIC
Equation)
PLT06
TBBKD
Time Between Breakers for Automatic Reclose
(1–99999 cycles)
300
1
BKCFD
Breaker Close Failure Delay
(OFF, 1–99999 cycles)
300
1
SLBK1
Lead Breaker = Breaker 1 (SEL
OGIC
Equation)
1
SLBK2
Lead Breaker = Breaker 2 (SEL
OGIC
Equation)
NA
FBKCEN
Follower Breaker Closing Enable
(SEL
OGIC
Equation)
1
ULCL1
Unlatch Closing for Breaker 1 (SEL
OGIC
Equation) 52AA1 AND
52AB1 AND
52AC1
ULCL2
Unlatch Closing for Breaker 2 (SEL
OGIC
Equation) 52AA2 AND
52AB2 AND
52AC2
79DTL
Recloser Drive to Lockout (SEL
OGIC
Equation)
NA
79BRCT
Block Reclaim Timer (SEL
OGIC
Equation)
NA
Table 8.73
Breaker 2 Synchronism Check (Sheet 2 of 2)
Setting
Prompt
Default
Value
Increment
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...