5.7
Date Code 20171021
Instruction Manual
SEL-421 Relay
Protection Functions
Current and Voltage Source Selection
SEL
OGIC
setting ALTV controls the switching between voltages VY and VZ for
line voltage (assert setting ALTV to switch to designated alternate line voltage
ALINEV := VZ). Setting ALTV is automatically hidden and set to NA if
ALINEV := NA (no voltage switching can occur). Reasons for switching from
one three-phase voltage to another may be for loss-of-potential or bus switching/
rearrangement.
Default line voltage source VY and alternate line voltage source settings
(ALINEV and ALTV) identify the voltages used in the following elements/fea-
tures described later in this section and in other sections:
➤
Fault location
➤
Open-phase detection logic
➤
LOP (loss-of-potential) logic
➤
FIDS (fault-type identification selection) logic
➤
Directional elements
➤
CVT (capacitor voltage transformer) transient detection logic
➤
Series-compensation line logic
➤
Load-encroachment logic
➤
OOS (out-of-step) logic
➤
Distance elements
➤
SOTF (switch-onto-fault) logic
➤
POTT (permissive overreaching transfer tripping) scheme logic
➤
, including synchrophasors
Default Applications
Use setting ESS (Current and Voltage Source Selection) to easily configure the
relay for your particular application. Five application settings (ESS := N, 1, 2, 3,
or 4) cover both single circuit breaker and two circuit breaker configurations. If
you select one of these five setting choices, the relay automatically determines
the following settings:
NOTE:
Setting BK2I is hidden if
setting NUMBK, Number of Breakers
in the Scheme, is set to 1.
➤
LINEI—Line Current Source (IW, COMB)
➤
BK1I—Breaker 1 Current Source (IW, IX, NA)
➤
BK2I—Breaker 2 Current Source (IX, COMB, NA)
2
3
VY
VZ or NA
2
4
VY
VZ or NA
a
NA = not applicable.
Shaded cells indicate settings forced to given values and hidden.
Table 5.4
Available Voltage Source Selection Setting Combinations
a
(Sheet 2 of 2)
NUMBK (number of
breakers)
ESS
(source selection)
Line Voltage Source
ALINEV (alternate
line voltage source)
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...