2.11
Date Code 20171006
Instruction Manual
SEL-400 Series Relays
PC Software
Create and Manage Relay Settings
Remote Data Acquisition Settings
In relays that support remote data acquisition, such as Time-Domain Link
(TiDL), there are configurable settings that are specific to those applications.
These settings are needed to help configure QuickSet and control attributes such
as setting ranges, defaults, and functionality. These settings are not part of the
actual relay firmware, and therefore are not sent to the relay at the time the set-
tings transfer. SECINC is one of these configurable settings. SECINC determines
the nominal current input for the remotely connected SEL-2240 Axion units used
in TiDL applications for remote data acquisition. In the relay, the user issues an
ASCII command,
CFG CTNOM
n
, to set the relay firmware to the correct nom-
inal current being received from the remote TiDL Axion units. Once the com-
mand has been used to set the nominal current value from the remote data
acquisition units, use QuickSet to set SECINC (see
) to that same nom-
inal value to adjust all QuickSet setting ranges to the appropriate scales.
Some relays, such as the SEL-487E, have multiple setting combinations. The
QuickSet settings for the SEL-487E, CURSTU and CURWXY, are shown in
. and are used instead of SECINC. For more information on the set-
tings options, review the
CFG CTNOM
command operation in
Section 2: Instal-
lation
of the product-specific instruction manual.
If at the time the relay settings are transferred, the QuickSet settings SECINC,
CURSTU, or CURWXY do not match the nominal current set in the relay by the
CFG CTNOM
command, the settings transfer is rejected and an error message is
displayed.
Figure 2.8
SECINC Setting
Figure 2.9
SEL-487E Nominal Current Selection
NOTE:
The relay must be configured
using the
CFG CTNOM
n
command
before the settings are transferred to
the relay to avoid erasing the
transferred settings. The commands
used to set the nominal current in the
relay will default all settings after the
commands are issued. Changing the
SECINC, CURSTU, or CURWXY
settings in QuickSet will not change
the rest of the settings in QuickSet
back to default but will provide an
error if any of the current settings are
now out of range. In addition, when
the relay is connected to QuickSet,
the software reads the configuration
of the relay and appropriately
updates this setting automatically;
however, this setting must work
offline and develop settings when not
connected to the relay.
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...