![Schweitzer Engineering Laboratories SEL-421-4 Instruction Manual Download Page 999](http://html.mh-extra.com/html/schweitzer-engineering-laboratories/sel-421-4/sel-421-4_instruction-manual_1216726999.webp)
6.23
Date Code 20171006
Instruction Manual
SEL-400 Series Relays
Autoreclosing
Two-Circuit-Breaker Autoreclosing
Single-Pole Trip Circuit Breakers
The initial settings necessary to enable autoreclose for two single-pole trip circuit
breakers are shown in
.
Recloser Mode Enables
The SEL
OGIC
control equations E3PR
n
and ESPR
n
set the relay for the three
autoreclose modes.
and
illustrate how to enable the autore-
close modes per circuit breaker.
Table 6.19
Two-Circuit-Breaker Three-Pole Reclose Initial Settings
Setting
Description
Entry
NUMBK
Number of Breakers in Scheme
2
Breaker Configuration (Breaker Monitor)
BK1TYP
a
a
Only applicable to products that support single-pole tripping and reclosing.
Breaker 1 Trip Type
3
BK2TYP
Breaker 2 Trip Type
3
Breaker 1 Inputs (Breaker Monitor)
52AA1
N/O Contact Input—BK1 (SEL
OGIC
Equation)
IN101
Breaker 2 Inputs (Breaker Monitor)
52AA2
N/O Contact Input—BK2 (SEL
OGIC
Equation)
IN102
Relay Configuration (Group)
E79
Reclosing
Y or Y1
Table 6.20
Two-Circuit-Breaker Single-Pole Reclose Initial Settings
Setting
Description
Entry
NUMBK
Number of Breakers in Scheme
2
Breaker Configuration (Breaker Monitor)
BK1TYP
Breaker 1 Trip Type
1
BK2TYP
Breaker 2 Trip Type
1
Breaker 1 Inputs (Breaker Monitor)
52AA1
A-Phase N/O Contact Input—BK1 (SEL
OGIC
Equation)
IN101
52AB1
B-Phase N/O Contact Input—BK1 (SEL
OGIC
Equation)
IN102
52AC1
C-Phase N/O Contact Input—BK1 (SEL
OGIC
Equation)
IN103
Breaker 2 Inputs (Breaker Monitor)
52AA2
A-Phase N/O Contact Input—BK2 (SEL
OGIC
Equation)
IN104
52AB2
B-Phase N/O Contact Input—BK2 (SEL
OGIC
Equation)
IN105
52AC2
C-Phase N/O Contact Input—BK2 (SEL
OGIC
Equation)
IN106
Relay Configuration (Group)
E79
Reclosing
Y or Y1
Table 6.21
Circuit Breaker BK1 Modes of Operation (Sheet 1 of 2)
E3PR1
ESPR1
a
Result
0
0
Autoreclose disabled
0
1
Single-pole autoreclose only enabled
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...