10.16
SEL-400 Series Relays
Instruction Manual
Date Code 20171006
Testing, Troubleshooting, and Maintenance
Relay Self-Tests
tion-disabled state. During a protection-disabled state, the relay suspends protec-
tion element processing and trip logic processing and de-energizes all control
outputs. When disabled, the
ENABLED
front-panel LED is not illuminated.
The relay signals a status warning by pulsing the HALARMP, HALARMA, and
HALARM Relay Word bits (hardware alarm) to logical 1 for five seconds. For a
status failure, the relay latches the HALARML and HALARM Relay Word bits
at logical 1. Some hardware failures prevent the relay from operating. In such
cases, Relay Word bits HALARML and HALARM do not assert.
Once HALARMP pulses, Relay Word bit HALARMA continues to assert for
approximately five seconds once per minute to indicate that a hardware warning
has occurred. HALARMA continues to pulse until it is reset by pulsing SEL
OGIC
control equation RST_HAL. Restarting the relay also resets HALARMA.
HALARMP does not assert again for the same alarm condition, unless the condi-
tion is cleared and returns.
The relay will automatically restart as many as two times on certain diagnostic
failures. In many instances, this will correct the failure. When this occurs, the
relay will log a
Diagnostic Restart
in the SER.
To provide remote status indication, connect the b contact of OUT108 to your
control system remote alarm input and program the output SEL
OGIC
control
equation to respond to NOT (SALARM OR HALARM).
If you repeatedly receive status warnings, check relay operating conditions as
soon as possible. Take preventive action early during the development of poten-
tial problems to avoid system failures. For any status failure, contact your Techni-
cal Service Center or the SEL factory immediately (see
).
The relay generates an automatic status report at the serial ports for a self-test sta-
tus failure if you set Port setting AUTO := Y. The relay issues a status message
with a format identical to the
STATUS
command output, but includes the power
supply information from the
STA A
response. The relay also displays status
warning and status failure automatic messages on the front-panel LCD. Use the
serial port
STATUS
and
CSTATUS
commands and the front-panel
RELAY STA-
TUS
menu to display status warnings and status failures. See
,
Checking Relay Status on page 3.11
, and
for more information on automatic status notifications and on viewing relay status.
The relay includes self-diagnostics that monitor settings, hardware, and commu-
nication. The settings diagnostic checks if an internal error may have caused the
calibration settings to be lost or corrupted, which would introduce errors in the
magnitude and angles of the voltages and currents measured. The hardware diag-
nostics monitor any component change that does not match the part number, as
well as hardware failures in the power supply, processors, and digital samplers.
For relays that support remote data acquisition, such as TiDL, the relay will mon-
itor the connection to the remote data or the communication board in the relay
that receives the remote data. Finally, the diagnostics monitor communications
such as Ethernet, serial, and 87L connections. The
STATUS
command notifies
the user if any of the diagnostics trigger a warning or a failure. In cases where the
issue is a failure the relay will become disabled and protection will be inhibited.
Status
is a sample
STATUS
screen from the Status option of the QuickSet
HMI > Meter and Control
tree view (the terminal
STATUS
report is similar).
is the
STATUS A
report showing all status information on a terminal.
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...