6.73
Date Code 20171021
Instruction Manual
SEL-421 Relay
Protection Applications Examples
345 kV Tapped Overhead Transmission Line Example
Zn is an approximation of the impedance calculation for the n-sequence voltage-
polarized directional statement for a reverse fault.
If z2 is less than Z2F during a reverse unbalanced fault, 32QG incorrectly
declares that the fault is forward with respect to the relay location (CT shown in
). The relay automatically sets Z2F equal to one-half Z1MAG.
is the apparent negative-sequence impedance z2 measured by the
32QG element during a reverse unbalanced fault.
Equation 6.41
The downstream parallel impedance, Z
2P
, is the Line 3 impedance, the trans-
former reactances, and the Bus R impedance.
Equation 6.42
Use the following two assumptions to simplify the calculations:
1. Assume the power system is purely reactive
2. Ignore source impedances Z
1R
and Z
1T
(a conservative assumption)
Figure 6.16
345 kV Tapped Line Negative-Sequence Network
where:
Z
2P
= parallel combination of the Line 3 impedance, transformer
reactances (neglect resistance), and the Bus T impedance with
Line 2 and the Bus R impedance
X
H
= transformer high-side winding reactance
X
M
= transformer low-side winding reactance
X
L
= transformer tertiary winding reactance
Z1T
ZM
ZH
S
Z1L3
Z1L2
Z1L1
I2
I2
Z1R
Z1S
R
T
SEL-421
z
0
Z
0L1
Z
0P
+
=
Z
2P
Z
1L3
jX
H
jX
M
jX
1T
+
+
+
=
Z
1L2
Z
1R
+
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...