![Schweitzer Engineering Laboratories SEL-421-4 Instruction Manual Download Page 44](http://html.mh-extra.com/html/schweitzer-engineering-laboratories/sel-421-4/sel-421-4_instruction-manual_1216726044.webp)
1.14
SEL-421 Relay
Instruction Manual
Date Code 20171021
Introduction and Specifications
Specifications
Specifications
Section 1Introduction and Specifications
Instruction Manual
Note:
If the relay uses a remote data acquisition system, such as TiDL, the
operating times will be delayed by 1.5 ms. Use caution when setting the
relay coordination times to account for this added delay. Element operate
times will also have this small added delay.
Compliance
Designed and manufactured under an ISO 9001 certified quality
management system
47 CFR 15B Class A
This equipment has been tested and found to comply with the limits
for a Class A digital device, pursuant to part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against
harmful interference when the equipment is operated in a
commercial environment. This equipment generates, uses, and can
radiate radio frequency energy and, if not installed and used in
accordance with the instruction manual, may cause harmful
interference in which case the user will be required to correct the
interference at his own expense.
UL Listed to U.S. and Canadian safety standards
(File E212775; NRGU, NRGU7)
CE Mark
General
AC Analog Inputs
Sampling Rate:
8 kHz
AC Current Inputs (Secondary Circuits)
Current Rating (With DC Offset at X/R = 10, 1.5 Cycles)
1 A Nominal:
18.2 A
5 A Nominal:
91 A
Continuous Thermal Rating
1 A Nominal:
3 A
4 A (+55°C)
5 A Nominal:
15 A
20 A (+55°C)
Saturation Current (Linear) Rating
1 A Nominal:
20 A
5 A Nominal:
100 A
A/D Current Limit
Note:
Signal clipping may occur beyond this limit.
5 A Nominal:
247.5 A
1 A Nominal:
49.5 A
One-Second Thermal Rating
1 A Nominal:
100 A
5 A Nominal:
500 A
One-Cycle Thermal Rating
1 A Nominal:
250 A-peak
5 A Nominal:
1250 A-peak
Burden Rating
1 A Nominal:
0.1 VA at 1 A
5 A Nominal:
0.5 VA at 5 A
AC Voltage Inputs
Three-phase, four-wire (wye) connections are supported.
Rated Voltage Range:
0–300 V
LN
Ten-Second Thermal
Rating:
600 Vac
Burden:
0.1 VA @ 125 V
Frequency and Rotation
Nominal Frequency
Rating:
50 ±5 Hz
60 ±5 Hz
Phase Rotation:
ABC or ACB
Frequency Tracking
Range:
40.0–65.0 Hz
<40 Hz = 40 Hz
>65.0 Hz = 65 Hz
Maximum Slew Rate:
15 Hz/s
Power Supply
24–48 Vdc
Rated Voltage:
24–48 Vdc
Operational Voltage
Range:
18–60 Vdc
Vdc Input Ripple:
15% per IEC 60255
-
26:2013
Interruption:
20 ms at 24 Vdc, 100 ms at 48 Vdc per
IEC 60255-26:2013
Burden:
<35 W
48–125 Vdc or 110–120 Vac
Rated Voltage:
48–125 Vdc, 110–120 Vac
Operational Voltage
Range:
38–140 Vdc
85–140 Vac
Rated Frequency:
50/60 Hz
Operational Frequency
Range:
30–120 Hz
Vdc Input Ripple:
15% per IEC 60255
-
26:2013
Interruption:
14 ms at 48 Vdc, 160 ms at 125 Vdc per
IEC 60255-26:2013
Burden:
<35 W, < 90 VA
125–250 Vdc or 110–240 Vac
Rated Voltage:
125–250 Vdc, 110–240 Vac
Operational Voltage
Range:
85–300 Vdc
85–264 Vac
Rated Frequency:
50/60 Hz
Operational Frequency
Range:
30–120 Hz
Vdc Input Ripple:
15% per IEC 60255
-
26:2013
Interruption:
46 ms at 125 Vdc, 250 ms at 250 Vdc per
IEC 60255
-
26:2013
Burden:
<35 W, < 90 VA
Control Outputs
Standard
Make:
30 A
Carry:
6 A continuous carry at 70°C
4 A continuous carry at 85°C
1 s Rating:
50 A
MOV Protection
(Maximum Voltage):
250 Vac, 330 Vdc
Pickup/Dropout Time:
6 ms, resistive load
Update Rate:
1/8 cycle
Break Capacity (10,000 Operations):
48 Vdc
0.50 A
L/R = 40 ms
125 Vdc
0.30 A
L/R = 40 ms
250 Vdc
0.20 A
L/R = 40 ms
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...