4.10
SEL-400 Series Relays
Instruction Manual
Date Code 20171006
Front-Panel Operations
Front-Panel Layout
Display Points
You can display messages on the relay front-panel LCD that indicate conditions
in the power system. The relay uses display points to place these messages on the
LCD.
shows a sample display points screen. Display points can show the
status of Relay Word bits or display the value of analog quantities. The relay has
96 possible display points;
and
list the display points settings.
The relay updates the display points data once per second if you are viewing the
display points in manual-scrolling mode; in autoscrolling mode the relay updates
the display points information each time the screen appears in the
ROTATING DIS-
PLAY
sequence.
To enable a display point, enter the display point settings listed in
. All display points occupy one, and only one, line on the display at all
times. The height of the line is determined by the “Text Size” setting parameter.
Display points of single-line height span one screen in total width. Display points
of double-line height span two screens in total width. You can use multiple dis-
play points to simulate multiple lines.
Use the following syntax to display the given Relay Word bit exactly as seen in
the navigational menu (name and value).
DPxx :=
Name
Use the following syntax to display the given Relay Word bit as seen in the navi-
gational menu, replacing the name of the value with the given alias string. The
text size determines if the display will be in single font or double font. If the text
size is empty, the display will be in single font.
DPxx :=
Name, “Alias”, “Text Size”
Example 4.1
Creating an Alarm Point (Continued)
Figure 4.11
Alarm Points Data Loss Screen
##SER DATA LOSS##
ALARM POINTS
Press to acknldge
Figure 4.12
Sample Display Points Screen
Circuit Breaker 1
--Closed--
DISPLAY POINTS
Circuit BK1 SF6 Gas
--Alarm--
Circuit Breaker 2
A PH= 119.6 A pri
SF6 ALARM
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...