396
System Manual – MOVIDRIVE® compact Drive Inverters
11
Operating displays of MCH42A (INTERBUS LWL)
Operation
LED RD "Remote
bus disable"
(yellow)
LED FO1 "Fiber
optic 1" (yellow)
LED FO2 "Fiber
optic 2" (yellow)
LED TR "Trans-
mit" (green)
LED TR "Trans-
mit" (yellow or red)
State
Meaning
Remedy
On
Outgoing remote bus switched off
-
Off
Outgoing remote bus not switched off
-
State
Meaning
Remedy
On
Monitoring of incoming fiber optic cable. If the
previous participant
•
has optical line diagnostics, the system
reserve for optical transmission has been
exceeded
•
does not have optical line diagnostics, a
control of the optical transmission power is
not possible
Check the incoming fiber optic cable for cable
quality, correct connector installation, bending
radius, etc. Use the special optical diagnostics
of the CMD tool or a fiber optic measurement
instrument for further localization of faults.
Off
Incoming fiber optic cable is functioning
properly
-
State
Meaning
Remedy
On
Monitoring of continuing fiber optic cable. If the
next participant
•
has optical line diagnostics, the system
reserve for optical transmission has been
exceeded
•
does not have optical line diagnostics, a
control of the optical transmission power is
not possible
Check the continuing fiber optic cable for
cable quality, correct connector installation,
bending radius, etc. Use the special optical
diagnostics of the CMD tool or a fiber optic
measurement instrument for further
localization of faults.
Off
Continuing fiber optic cable is functioning
properly
-
State
Meaning
Remedy
The green color of the LED TR corresponds to the INTERBUS standard.
Off
No PCP communication
-
Green
PCP communication is active or INTERBUS startup (parameter access
via INTERBUS PCP channel)
-
State
Meaning
Remedy
The LED TR indicates states within the system that usually do not occur during INTERBUS operation.
Off or green Normal operation (see table for TR = green)
-
Yellow
Flashing
Inverter is currently in the initialization phase
-
Red
Continuous
Incorrect DIP switch configuration selected,
INTERBUS operation is not possible.
Check the settings of the DIP switches S1.
Correct the DIP switch settings, if necessary,
and switch the unit on again.
Flashing
red
Incorrect DIP switch configuration or INTER-
BUS interface defective, INTERBUS operation
is not possible.
Check the position of DIP switches S1 to S6. If
the settings are correct, contact the SEW
Electronics Service.
Summary of Contents for MOVIDRIVE compact MCH41A
Page 2: ...SEW EURODRIVE Driving the world...
Page 432: ......