Startup with the DBG11B keypad
Startup
Startup
procedure
1. Enter a "0" signal at terminal DIØØ "/CONTROLLER INHIBIT".
CONTROLLER INHIBIT
CURRENT:
0 A
2. Activate the startup menu by pressing the
←
and
→
keys on
the DBG11B at the same time.
STARTUP PARAMET.
→
IPOS_VARIABLES
←
3. Press the
→
key to commence startup. The first window of the
startup menu appears. The menu items are indicated with a *
as the fourth character. Menu items that only appear in the star-
tup menu start with a *. The other menu items have the number
of the parameter list (page 342). Once you have finished with a
menu item, use the
↑
key to go to the next menu item.
STARTUP PARAMET.
PREPARE FOR STARTUP
4. Select a parameter set, e.g. parameter set 1.
C00*
PARAM. SET 1
STARTUP PARAMET.
5. Set the operating mode, e.g. VFC1.
C01*
VFC1
OPERATING MODE 1
6. Select the connected motor. If a 2 or 4-pole SEW motor is
connected, select the correct motor from the list. If a non-SEW
motor or an SEW motor with more than four poles is connected,
select "NON-SEW MOTOR" from the list.
C02*
DV112M4
MOTOR TYPE 1
C02*
NON-SEW
MOTOR
MOTOR TYPE 1
7. Enter the rated motor voltage for the selected connection type
according to the value specified on the nameplate.
Example: Nameplate 230
∆
/400
댴
50 Hz
댴
connection
→
Enter "400 V".
∆
connection, transition point at 50 Hz
→
enter "230 V".
∆
connection, transition point at 87 Hz
→
Also enter "230 V".
However, after startup first set parameter P302 "MAXIMUM
SPEED 1" to the value for 87 Hz and then start the drive.
Example: Nameplate 400
∆
/690
댴
50 Hz
Only
∆
connection possible
→
Enter "400 V".
댴
connection is not possible.
C03*
400
V
RATED MOTOR VLTG 1
8. Enter the rated frequency specified on the motor nameplate.
Example: 230
∆
/400
댴
50 Hz
Enter 50 Hz in
댴
and
∆
connection.
C04*
50
Hz
RATED MOTOR FREQ. 1
FOR SEW MOTORS
9. The motor values are stored for SEW 2 and 4-pole motors and
need not be entered.
FOR NON-SEW MOTORS
9. Enter the following motor nameplate data:
•
Rated motor current, note the connection type (
댴
or
∆
).
•
Rated power of the motor
•
Power factor cos
ϕ
•
Rated speed of the motor
10. Enter the rated mains voltage.
C05*
400
V
RATED MAINS VLTG 1
11. If a TF/TH is not connected
→
set "NO RESPONSE." If a
TF/TH is connected, set the required fault response.
835*
NO RESPONSE
RESP. TF SIGNAL
0
0
I