System Manual – MOVIDRIVE® compact Drive Inverters
10
Starting up the inverter with INTERBUS (MCH42A)
Startup
The following table shows the possible settings. The ID code setting must match the DIP
switches S4 and S5. The process data channel setting must match the DIP switches S1
to S3, otherwise, INTERBUS operation is not possible.
Information for
offline configura-
tion in the CMD
tool
Online configura-
tion: Configuration
frame / Read in
The INTERBUS system can also be installed completely at first, and then the DIP
switches S1 to S6 can be set. Next, the CMD tool can be used to read in the entire bus
structure (configuration frame). All devices are automatically detected with their data
width settings.
NOTE
Not all combinations are possible because the inverter can occupy a maximum of six
words in the INTERBUS.
Program settings
Function (MOVIDRIVE
®
display)
ID code
227 dec (E3 hex)
Parameter channel: 1 word
Process data
channel:
16 bit
1 process data word (param+1PD)
32 bit
2 process data words (param + 2 PD)
48 bit
3 process data words (param + 3 PD)
64 bit
4 process data words (param + 4 PD)
80 bit
5 process data words (param + 5 PD)
ID code
224 dec (E0 hex)
Parameter channel: 2 words
Process data
channel:
16 bit
1 process data word (param+1PD)
32 bit
2 process data words (param + 2 PD)
48 bit
3 process data words (param + 3 PD)
64 bit
4 process data words (param + 4 PD)
ID code
225 dec (E1 hex)
Parameter channel: 4 words
Process data
channel:
16 bit
1 process data word (param+1PD)
32 bit
2 process data words (param + 2 PD)
ID code
3 dec (03 hex)
Parameter channel: -
Process data
channel:
96 bit
6 process data words (6PD)
0
0
I