162
System Manual – MOVIDRIVE® compact Drive Inverters
3
Explanation of the parameters
Parameters
Connection check
In manual operation a connection check always takes place between DBG11B and the
inverter or between USS21A/USB11A and the inverter. Parameter P812 RS485 Time-
out delay has no function. The inverter must receive a valid RS485 telegram within the
fixed time interval of t = 500 ms. If the time is exceeded, the drive is stopped at the emer-
gency stop ramp and error message F43 "RS485 timeout" is issued.
P880 Manual
operation
Setting range: ON / OFF
•
ON: Manual operation is activated.
•
OFF: No manual operation.
P9xx IPOS parameters
The IPOS
plus®
parameters are described in detail in the IPOS
plus®
manual.
P90x IPOS
Reference travel
Reference travel is used to establish a machine zero to which all absolute positioning
commands refer. You can select different reference travel strategies in P903 Reference
travel type . These strategies define appropriate travel modes, for example to search for
a reference cam. Based on the reference point established through the reference trav-
el, you can use P900 Reference offset to shift the machine zero according to the equa-
tion
Machine zero = reference po reference offset
The speeds for the necessary travel movements according to reference travel type are
set with P901 Reference speed 1 / P902 Reference speed 2 .
P900 Reference
offset
Setting range: –(2
31
–1) ... 0 ... 2
31
–1
Reference offset (zero offset) is used to determine the machine zero (origin). The follow-
ing applies:
Machine zero = reference po reference offset
The reference offset always refers to the encoder set via P941 Source actual position
when the modulo function is deactivated (P960 = OFF).
This can be either the motor encoder or an external encoder. The corresponding actual
positions are indicated by IPOS
plus®
variables.
•
H510 Actual position external encoder
•
H511 Actual position motor encoder
NOTE
The error is automatically reset and the drive enabled when the inverter receives a valid
telegram again.
DANGER!
Risk of crushing if the motor starts up unintentionally.
Severe or fatal injuries.
•
Ensure that the motor cannot start unintentionally.
•
Note that modifying IPOS
plus®
parameters without knowledge of the IPOS
plus®
pro-
gram, which may be active, can cause unexpected movements and place unwanted
loads on the mechanical driveline. It is essential that you are familiar with the
IPOS
plus®
manual to make the setting for these parameters.
P6..
P60.
P600