Explanation of the parameters
Parameters
The result is the following nominal guide value for detection of a phase failure:
•
50 Hz power supply: ca. t
max
= 3.0 s
•
60 Hz power supply: ca. t
max
= 2.5 s
Once a phase failure has been detected, the output stage is inhibited and the brake is
applied. The error message
F06 Phase failure
is displayed. The error response is as fol-
lows: Immediate switch-off with inhibit. The error can only be remedied by executing a
unit reset.
P53x Temperature protection motor
P530 Sensor type
1
Setting values: No sensor / TF-TH
Selection of the sensor used for motor protection in parameter set 1. Set the response
with P835 Response TF SIGNAL.
P531 Sensor type
2
Setting values: No sensor / TF-TH
Selection of the sensor used for motor protection in parameter set 2.
P6..
P60.
P600