286
System Manual – MOVIDRIVE® compact Drive Inverters
9
Installation notes for PROFIBUS-DP interface (MC_41A)
Installation
Setting the sta-
tion address for
MCF/MCV/MCS41
A
The PROFIBUS station address is set using DIP switches 4...10 (significance 2
6
... 2
0
)
under the connection unit (
→
Sec. "Removing the connection unit" on page 304).
MOVIDRIVE
®
compact
supports the address range 0 to 125.
The PROFIBUS station address can only be set using the DIP switches when the con-
nection is removed. Therefore, the address cannot be changed during operation. The
change only comes into effect when the drive inverter is switched on again (power
DC 24 V OFF/ON). The drive inverter displays the current station address in
fieldbus monitor parameter P092 "Fieldbus address" (display with DBG11B or
MOVITOOLS/SHELL).
Example: Setting station address 17
02895AEN
Figure 100: Setting the PROFIBUS station address for MCF/MCV/MCS41A
03003AEN
Figure 101: Setting station address 17
1
2
3
4
5
67
8
9
1
0
2
0
2
1
2
2
2
3
2
4
2
5
2
6
nc
TERMINATION
R
ON
OFF
ON
1
2
R
ON
mA
V
S12
S11
Significance: 1 x 0 = 0
Significance: 2 x 0 = 0
Significance: 4 x 1 = 4
Significance: 8 x 0 = 0
Significance: 16 x 0 = 0
Significance: 32 x 0 = 0
Significance: 64 x 0 = 0
Factory setting:
Address = 4
Not connected, position OFF
PROFIBUS-DP Bus termination
Significance ON
1
2
3
4
5
67
8
9
1
0
2
0
2
1
2
2
2
3
2
4
2
5
2
6
nc
TERMINATION
R
ON
OFF
ON
1
2
R
ON
mA
V
S12
S11
1 x 1 = 1
2 x 0 = 0
4 x 0 = 0
8 x 0 = 0
16 x 1 = 16
32 x 0 = 0
64 x 0 = 0
Significance:
Significance:
Significance:
Significance:
Significance:
Significance:
Significance:
For example:
Set address = 17
Not connected, position OFF
PROFIBUS-DP Bus termination
Significance ON
Summary of Contents for MOVIDRIVE compact MCH41A