Operating modes
Parameters
VFC 1 / 2 & Flying
start
The flying start function lets you synchronize the inverter to a motor that is already run-
ning. In particular used with drives that are not braked actively, which run on for a long
time or which are turned by a flowing medium, e.g. pumps and fans. The maximum flying
start time is approx. 200 ms.
If the inverter does not detect a trap point, it assumes a motor at rest and starts the in-
tegrator at n = 0. This process is characterized by braking of the motor to n = 0 and sub-
sequent acceleration to n
setpt
. This behavior may arise in particular with very low resis-
tance motors in the speed range below n=300 1/min (4-pole motor).
01308CEN
Figure 55: VFC & flying start function
DANGER!
Risk of crushing if the motor starts up unintentionally in hoist applications.
Severe or fatal injuries.
•
Do not use the flying start function in hoist applications!
•
Ensure that the motor cannot start unintentionally.
NOTE
The flying restart function does not function if there is an output filter connected to the
inverter.
P6..
P60.