The expert characteristic curves displayed in Figure 33 are created as follows:
Expert characteristic curve with current setpoints:
Voltage signals are required at the AI11/AI12 analog input for the expert characteristic
curve function. If a load-independent current 0 (4)...20 mA is available as setpoint,
switch S11 (changeover I-signal/V-signal) must be set to ON and the current signal rout-
ed to X11:2 AI11. The setpoints 0 (4) ...20 mA will be converted into voltage signals 0
(1) ... 5 V through the internal burden (250
Ω
) .
If you want to achieve speeds of 1000 ... 4000 1/min with 0 (4) ... 20 mA, you will have
to set 4000 1the expert characteristic curve as follows:
Set P100 Setpoint source = UNIPOL/FIX.SETPT. The direction of rotation is then spec-
ified using binary inputs.
Characteristic
curve
1
0
0
1
2
4
500
1.39
3
0
1500
1
4
0
3000
–1.25
02165BEN
Figure 34: Sample expert characteristic curves with current setpoints
for 0 ... 20 mA:
P110 = 2
P113 = 0 V
P114 = 1000 1/min
P302 (n
max
) = 4000 1/min
for 4 ... 20 mA:
P110 = 2.5
P113 = 1 V
P114 = 1000 1/min
P302 (n
max
) = 4000 1/min
10V
-10V
2V
4V
6V
8V
-2V
-4V
-6V
-8V
0V
n
=
4000
ma x
5000
5500
2000
3000
1000
-2000
-1000
-n
=
-4000
ma x
-5000
-5500
-3000
0
n P114
V
P113
I
Direction of
rotation = "CW"
Direction of
rotation = "CCW"
[rpm]
0 – 20 mA
4 – 20 mA
P6..
P60.
P600