MICROMASTER Drives 6SE92
Getting Started
Caution: Before installing and
putting this equipment into
operation, please read the
Operating Instructions Manual for
Safety Precautions and Warnings
SIEMENS MICROMASTER
The MICROMASTER products are a range of frequency
inverters for controlling the speed of three phase AC
induction motors
Step 1 Connecting up the MICROMASTER
230V Single Phase 400V Three Phase
Delta connection for
230V 3 phase
Star connection for
400V 3 phase
Note: Motors above 11kW are usually configured
400V Delta / 690V Star.
In this case the motor should be connected in Delta.
At any time, press the 'STOP' button and watch the
motor stop.
Step 3 Changing the speed of the motor
Step 2 Getting the motor going
The default output frequency of the drive is 5Hz (see
Hints and Tips
to convert this to RPM). This speed will
probably be too low for most applications and a speed
change may be required. The following steps will allow
you to change the preset value of the inverter output to
the required speed.
Step / Action
Display
Press the 'P' button to access the parameter settings.
P000
P005
005.0
035.0
P005
P000
000.0
035.0
Press the
button 5 times until the display reads P005.
Press the 'P' button to display the current parameter value.
Press the button to change the value to 35Hz. (This
number can be any number between 0 and 50Hz - default.)
Press the 'P' button to store the new value.
Press the
button until the display reads P000.
Press the 'P' button to exit the parameterisation procedure.
The display will alternate between the output frequency and
the frequency set point.
The required speed has now been stored.
This method is used to access all parameters.
The drive can now be started by pressing the '
RUN
'
button. It will ramp up to the frequency held in parameter
P005
and remain there. To stop the drive press the
'
STOP
' button, the drive will then ramp down to 0Hz
output.
Default Parameters:
Digital input
Parameter
Terminal
Default
1
2
3
5
6
7
P051 = 1
P052 = 2
P053 = 6
ON right
ON left
Fixed
Frequency
Output
Relay 1
10/11
P061 = 6
Fault
Identification
Fault Codes:
Motor overtemperature by I²t
calculation
Other faults, see manual
F001
F002
F003
F005
F074
Overvoltage
Overcurrent
Overload
Inverter overtemperature
(internal PTC)
http://www.con.siemens.co.uk
For further Technical Support
Information, and to submit your
suggestions for improvements,
see our Web Site: