Starting up the inverter with INTERBUS (MCH42A)
Startup
The inverter now executes the service coded in the parameter channel and re-enters the
service confirmation in the parameter channel. The master receives the service
confirmation with the next read access to the "MOVILINK
®
cyclic parameter channel."
The following table shows the process of the cyclically called read/write services for the
"MOVILINK cyclic parameter channel."
Controller (master)
MOVIDRIVE
®
(slave)
1. "READ MOVILINK
®
cyclic parameter channel" to evaluate the status of the handshake bit.
READ 8298 (parameter channel)
Data = parameter channel
2. Initiate execution of the service coded in the parameter channel with WRITE on the "MOVILINK
®
cyclic
parameter channel" object and the handshake bit toggle.
WRITE 8298 (parameter channel)
OK
3. READ "MOVILINK
®
cyclic parameter channel" and evaluation of service confirmation in the parameter
channel.
READ 8298 (parameter channel)
Data = parameter channel with result
0
0
I