System Manual – MOVIDRIVE® compact Drive Inverters
49
2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
MOVIDRIVE® compact MCF/MCV/MCS electronics data
Technical Data and Dimension Drawings
2.5
MOVIDRIVE
®
compact MCF/MCV/MCS electronics data
MOVIDRIVE
®
compact
Setpoint processing and speed ramps
MCF/MCV/MCS40A
and MCV/MCS41A
Version with analog setpoint input
Voltage supply
X10:1
for setpoint input
X10:3
REF1: DC+10 V +5 % / –0 %, I
max
= DC 3 mA
REF2: DC–10 V +0 % / –5 %, I
max
= DC 3 mA
Reference voltages for setpoint potentiom-
eter
Setpoint input n1
X10:2/X10:4
AI11/AI12: Voltage or current input, can be set with S11 and P11_, sampling interval 1 ms
(Differential input)
Operating mode AI11/AI12
Resolution
Internal resistance
Voltage input:
n1 = DC (0...+10 V) or DC (–10 V...0...+10 V)
12 bit
R
i
= 40 k
Ω
(external voltage supply)
R
i
= 20 k
Ω
(supply from REF1/REF2)
Current input:
n1 = DC (0...20 mA) or DC (4...20 mA)
11 bit
R
i
= 250
Ω
MCF/MCV/MCS41A (X10:2 and X10:4
inactive for MCF41A)
Version with PROFIBUS-DP interface. No analog setpoint input n1 (AI11/AI12) available
for MCF41A; setpoint selection only via PROFIBUS-DP interface.
Protocol variant
Baud rate
Connection technology
Bus terminator
Station address
Name of the GSD file
DP ident. number
PROFIBUS DP to IEC 61158
Automatic baud rate detection from 9.6 kbaud to 12 Mbaud
9-pole sub D connector, pin assignment to IEC 61158
Can be activated for cable type A to IEC 61158
0 ... 125, adjustable via DIP switches
SEW_6002.GSD
6002
hex
(24578
dec
)
Valid for all versions
Setpoint input n2
X10:6
TF/TH input
Resolution
Analog input DC (0 ... 10 V) or optionally (
→
P120) TF/TH input
with response threshold at R
TF
≥
2.9 k
Ω
±
10 %
10 bit
Internal setpoints
Parameter set 1: n11/n12/n13 = –5000...0...+5000 min
–1
Parameter set 2: n21/n22/n23 = –5000...0...+5000 min
–1
Time ranges of the speed ramps
at
∆
n = 3000 min
–1
1. Ramp
t11/t21
Up: 0.0...2000 s
Down: 0.0...2000 s
2. Ramp
t12/t22
Up = down: 0.0...2000 s
Stop ramp
t13/t23
Down: 0...20 s
Emergency ramp
t14/t24
Down: 0...20 s
Motor potentiometer
t3
Up: 0.2...50 s
Down: 0.2...50 s
P
i
f
kVA
Hz
n
Summary of Contents for MOVIDRIVE compact MCH41A
Page 2: ...SEW EURODRIVE Driving the world...
Page 432: ......