Installation notes for PROFIBUS-DP interface (MC_41A)
Installation
Setting the sta-
tion address with
MCH41A
The PROFIBUS station address is set using DIP switches 1 ... 8 (significance 2
0
... 2
6
)
under the connection unit (
→
Sec. "Removing the connection unit" on page 304).
MOVIDRIVE
®
compact
supports the address range 0 to 125.
The PROFIBUS station address can only be set using the DIP switches when the con-
nection is removed. Therefore, the address cannot be changed during operation. The
change only comes into effect when the drive inverter is switched on again (power
DC 24 V OFF/ON). The drive inverter displays the current station address in
fieldbus monitor parameter P092 "Fieldbus address" (display with DBG11B or
MOVITOOLS/SHELL).
Example: Setting station address 17
05527AEN
Figure 102: Setting the PROFIBUS station address with MCH41A
05528AEN
Figure 103: Setting station address 17