Explanation of the parameters
Parameters
P88x Manual operation (only available with the DBG11B keypad)
The inverter is controlled using the DBG11B keypad with the manual operation function.
To start manual operation the inverter must be assigned the status "No enable." The
state "No enable" means DIØØ/Controller inhibit = "1" and the binary inputs CW/stop,
DIØ2 CCW/stop and DIØ3 Enable/stop with programmed factory settings = "0".
The binary input DIØØ/Controller inhibit is also in effect in manual operation. The other
binary inputs are not in effect during manual operation. Binary input DIØØ/Controller in-
hibit must be assigned a "1" signal to enable the drive to be started in manual operation.
The drive can also be stopped in manual operation by setting DIØØ to "0". The direction
of rotation is not determined by the "CW/stop" or "CCW/stop" binary inputs. Instead, you
select the direction of rotation using the keypad.
Manual operation remains active when the power supply is switched off and on; howev-
er, the inverter is then inhibited. Setting the direction of rotation with the [
→
] key or [
←]
key enables and starts the drive with n
min
in the selected direction. The speed is in-
creased and decreased using the [
↑
] and [
↓]
keys. The rate of change is 150 1/min per
second.
02406AEN
Figure 52: Manual operation with DBG11B
↓
-key: decrease speed
↑
-key: increase speed
Q-key
Q-key
E-key
↑
↓
- or -key
→
-key
880
_OFF
MANUAL OPERATION
88
OFF
MANUAL OPERATION
0
_ DIR. OF ROTATION
L
<E>=EXIT
R
_ 0%In
0 rpm
<Q>=STOP
R
_ 0%In
0 rpm
L
<Q>=STOP
←
-key
←
-key
←
-key
→
-key
→
-key
NOTE
The signals at the binary inputs take effect as soon as manual operation is finished.
Binary input DIØØ/Controller inhibit does not have to be switched from "1" to "0" and
back to "1". The drive can start according to the signals at the binary inputs and the
setpoint sources.
Check that the programmed binary inputs DIØ1 CW/stop, DIØ2 CCW/stop and DIØ3
Enable/rapid stop are assigned a "0" signal when you end manual operation.