System Manual – MOVIDRIVE® compact Drive Inverters
4
Supply system cables and motor cables
Project Planning
Permitted motor
cable lengths
The maximum motor cable length depends on:
•
Cable type
•
Voltage drop in the cable
•
Set PWM frequency P860/P861.
•
An HF... output filter can only be connected for VFC operating mode. If an HF... out-
put filter is connected, the cable length is not restricted by these limit values, but ex-
clusively by the voltage drop along the motor cable.
•
For encoder connection (VFC-n, CFC, SERVO): Maximum cable length for the en-
coder connection is 100 m at a capacitance per unit length
≤
120 nF/km.
The following data applies as an approximation:
MOVIDRIVE
®
compact MC_4_A...-5_3:
MOVIDRIVE
®
compact MC_4_A...-2_3:
MC_4_A...-5_3
At V
mains
= 3
×
AC 400 V
0015
0022
0030
0040
0055
0075 ... 0750
Recommended maximum motor cable length [m]
Shielded line
VFC operating mode
1)
4 kHz
PWM frequency
8 kHz
(P860/P861)
12 kHz
16 kHz
1) An output filter is only permitted in the VFC operating mode and with an unshielded motor cable. If an HF... output filter is connected,
the cable length is not restricted by these limiting values, but exclusively by the voltage drop along the motor cable.
120
80
50
40
200
120
80
60
250
150
120
100
300
250
200
150
300
250
200
150
400
300
250
200
CFC and SERVO operating modes
PWM frequency fixed to 8 kHz
100 (330)
Unshielded line
VFC operating mode
4 kHz
PWM frequency
8 kHz
(P860/P861)
12 kHz
16 kHz
360
240
150
120
600
360
240
180
750
450
360
300
900
750
600
450
900
750
600
450
1200
900
750
600
CFC and SERVO operating modes
PWM frequency fixed to 8 kHz
100
MC_4_A...-2_3
At V
mains
= 3
×
AC 230 V
0015
0022
0037
0055
0075
0110 ... 0300
Recommended maximum motor cable length [m]
Shielded line
VFC operating mode
1)
4 kHz
PWM frequency
8 kHz
(P860/P861)
12 kHz
16 kHz
1) Do not connect an output filter to MOVIDRIVE
®
MC_4_A...-2_3!
120
80
50
40
200
120
80
60
250
150
120
100
300
250
200
150
300
250
200
150
400
300
250
200
CFC operating mode
PWM frequency fixed to 8 kHz
100
Unshielded line
VFC operating mode
4 kHz
PWM frequency
8 kHz
(P860/P861)
12 kHz
16 kHz
360
240
150
120
600
360
240
180
750
450
360
300
900
750
600
450
900
750
600
450
1200
900
750
600
CFC operating mode
PWM frequency fixed to 8 kHz
100