84
System Manual – MOVIDRIVE® compact Drive Inverters
2
Output filter HF...
Technical Data and Dimension Drawings
2.18
Output filter HF...
HF... output filters are sine filters used to smooth output voltage from inverters. HF... out-
put filters (with the exception of HF450-503) are approved to UL/cUL in combination with
MOVIDRIVE
®
drive inverters. HF... output filters are used in the following cases:
•
In group drives (several motor cables in parallel); the discharge currents in the motor
cables are suppressed.
•
To protect the motor winding insulation of non-SEW motors which are not suitable for
inverters
•
For protection against overvoltage peaks in long motor cables (> 100 m).
NOTES
•
Output filters can only be operated in V/f and VFC operating modes. Do not use out-
put filters in CFC / SERVO operating modes.
•
Do not use output filters in hoist applications.
•
During project planning of the drive, take the voltage drop in the output filter into ac-
count and the reduced motor torque that results. This applies particularly to AC 230
V units with output filters.
Output filter type
HF015-503
1)
HF030-503
HF055-503
Part number
826 030 3
826 031 1
826 032 X
826 311 6
826 312 4
Rated voltage
U
N
3
×
AC 380 V –10 % ... 3
×
AC 500 V +10 %, 50/60 Hz
2)
Earth-leakage current at V
N
∆
I
0 mA
Power loss at I
N
P
V
35 W
55 W
65 W
90 W
115 W
Interference emission via
unshielded motor cable
According to class B limit to EN 55011 and EN 55014
complies with EN 50081, parts 1 and 2
Ambient temperature
ϑ
U
0 °C ... +45 °C (reduction: 3 % I
N
per K to max. 60 °C)
Enclosure (EN 60529)
IP20
Connections/
tightening torque
M4 terminal studs
1.6 Nm
±
20 %
Weight
4.4 kg
10.8 kg
Assignment to AC 400/500 V units (...-5_3)
Voltage drop at I
N
∆
V
< 6.5 % (7.5 %) at AC 400 V / < 4 % (5 %) at AC 500 V and f
Amax
= 50 Hz (60 Hz)
Rated through current
3)
I
N 400 V
(at V
mains
= 3
×
AC 400 V)
I
N 500 V
(at V
mains
= 3
×
AC 500 V)
AC 4 A
AC 3 A
AC 6 A
AC 5 A
AC 8 A
AC 6 A
AC 10 A
AC 8 A
AC 12 A
AC 10 A
Rated operation (100 %)
0015
0022
0030
0040
0055
-
0015
0022
0030
0040
Assignment to AC 230 V units (...-2_3)
Voltage drop at I
N
∆
V
< 18.5 % (19 %) at AC 230 V with f
Amax
= 50 Hz (60 Hz)
I
N 230 V
(at V
mains
= 3
×
AC 230 V)
AC 6.5 A
AC 10.8 A
AC 13 A
AC 17.3 A
AC 22 A
Rated operation (100 %)
-
0015/0022
-
0037
0055
-
0015/0022
-
-
0037
1) UL/cUL approval in combination with MOVIDRIVE
®
drive inverters. SEW-EURODRIVE will provide certification on request.
2) A reduction of 6 % I
N
per 10 Hz applies above f
AN
= 60 Hz for the rated through current I
N
.
3) Only applies for operation without V
DC link
connection. For operation with V
DC link
connection, observe the project planning instructions
in the MOVIDRIVE
®
compact
system manual, section "Project Planning/Connecting the optional power components."
P
i
f
kVA
Hz
n