System Manual – MOVIDRIVE® compact Drive Inverters
10
Starting up the inverter with INTERBUS (MCH42A)
Startup
Reading a drive
parameter
The "Read" service is used for reading a drive parameter (with index
≤
8800). All drive
parameters are generally 4 bytes long (1 double word).
Example
Reading P130 ramp t11 UP CW (index 8470dec = 2116hex)
Once you have sent this service, you should receive the positive message
"Read_Confirmation".
The parameter data are represented in Motorola format (Simatic format) as follows:
00 00 07 D0 hex = 2000 dec(= 2000 ms ramp)
Refer to the appendix in the "MOVIDRIVE
®
Fieldbus Unit Profile" manual for more
information on coding drive parameters.
The table shows the "Value for parameter too great" return code, by way of example.
Word
Meaning
Coding (hex)
1
Command_Code = Read_Request
00 81
2
Parameter_Count
00 03
3
Invoke_ID
Comm._Reference
00 02
4
Index
21 16
5
Subindex
-
00 00
Bits
15 ... 8
7 ... 0
Word
Meaning
Coding (hex)
1
Message_Code = Read_Confirmation (+)
80 81
2
Parameter_Count
00 05
3
Invoke_ID
Comm._Reference
00 02
4
Result (+)
00 00
5
-
Length
00 04
6
Data [1]
Data [2]
00 00
7
Data [3]
Data [4]
07 D0
Bits
15 ... 8
7 ... 0
Data [1] = High Byte
Data [2] = Low Byte
Data [3] = High Byte
Data [4] = Low Byte
00 hex
00 hex
07 hex
D0 hex
Word
Meaning
Coding (hex)
1
Message_Code = Read_Confirmation
80 81
2
Parameter_Count
00 03
3
Invoke_ID
Comm._Reference
00 02
4
Error_Class
Error_Code
08 00
5
Additional_Code
00 10
Bits
15 ... 8
7 ... 0
0
0
I