Explanation of the parameters
Parameters
•
MOTOR POT.: The setpoint is generated by the internal motor potentiometer. For
this purpose, one binary input must be programmed to MOTOR.POT. UP and anoth-
er binary input to MOTOR.POT. DOWN, and the binary inputs must be activated
accordingly. The direction of rotation is specified by the clockwise/stop and counter-
clockwise/stop binary inputs. See P15x Motor potentiometer.
•
MANALOG1: The setpoint is defined by the total of the motorized poten-
tiometer and the setpoint selection at analog input AI1. The analog setpoint is pro-
cessed as a signed setpoint. If the sum is negative, n
min
applies. The direction of
rotation is specified using binary inputs. The settings of P112 AI1 Operating mode.
See P15x Motor potentiometer.
•
FIX SETP+ANALOG1: The setpoint is defined by the total of the selected fixed set-
point and the setpoint selection at analog input AI1. The fixed setpoint is processed
without sign (= according to its value) and the analog setpoint is processed as a
signed setpoint. If the total is negative or if a fixed setpoint has not been selected,
n
min
applies. The direction of rotation is specified using binary inputs. See P16x
•
FIXEDSETxANALOG1: The value at the analog input AI1 serves as an evaluation
factor (0 ... 10 V = 0 ... 100 %) for the selected fixed setpoint. The fixed setpoint is
processed without sign (= according to the value). If the voltage at analog input AI1
is negative or if no fixed setpoint is selected, n
min
applies. The direction of rotation is
specified using binary inputs. See P16x Fixed setpoints 1.
•
MASTER SBus: The setpoint comes from the master in master/slave mode via the
system bus. See P75x Master-Slave function.
•
MASTER-RS485: The setpoint comes from the master in master/slave mode via the
RS485 interface. See P75x Master-Slave function.
•
SBus: The setpoint is selected via the system bus. See IPOS
plus®
manual.
P101 Control
signal source
This parameter is used to set the source of the control signals for the inverter (CON-
TROLLER INHIBIT, ENABLE, CW, CCW, ...). Control via IPOS
plus®
is taken into
account regarless of P101.
•
TERMINALS: Control is performed via the binary inputs.
•
RS485: Control is performed via the RS485 interface and the binary inputs.
•
FIELDBUS: Control is performed via the fieldbus and the binary inputs.
•
SBus: Control is performed via the system bus and the binary inputs.