304
System Manual – MOVIDRIVE® compact Drive Inverters
9
Removing the connection unit
Installation
9.8
Removing the connection unit
For simple installation of the control leads, remove the entire connection unit from the
control unit. You have to remove the connection unit to set the DIP switches for
PROFIBUS (1 ... 10), INTERBUS (S1...S6), signal switchover n1 (S11) and SBus termi-
nating resistor (S12). Proceed as follows:
1. Open the panel of the connection unit.
2. Loosen retaining screws A and B; they are captive screws and cannot fall out.
3. Remove the connection unit from the control module.
Follow the instructions in reverse order when installing the connection unit.
NOTE
Turn off the supply voltage and DC-24 V auxiliary voltage before removing the connec-
tion unit.
60111AXX
A
B
1.
3.
2.