Explanation of the parameters
Parameters
P814 SBus group
address
Setting range: 0 ... 63
P814 is used to set the system bus group address (for multicast telegrams) of the
MOVIDRIVE
®
unit.
P815 SBus timeout
delay
Setting range: 0 ... 650 s
P815 sets the monitoring time for data transmission via the system bus. If no data traffic
takes place via the system bus during the period set in P815, MOVIDRIVE
®
executes
the error response set in P836 . Data transferred via system bus is not monitored when
P815 is set to 0.
P816 SBus baud
rate
Setting range: 125 / 250 / 500 / 1000 kBaud
P816 sets the transmission speed of the system bus.
P817 SBus
synchronization ID
Setting range: 0 ... 2047
The drives can be synchronized for transmitting process data and parameter data via
the system bus. To do so, the master controller must send a synchronization telegram
to the connected inverters at certain intervals. In this way, the inverters synchronize
themselves to the master controller. P817 is used for setting the identifier (address) of
the synchronization message in the inverter for the system bus. Make sure there is no
overlap between the identifiers for the process data or parameter data telegrams.
P818 CAN
synchronization ID
Setting range: 0 ... 1 ... 2047
The drives can be synchronized for transmitting process data and parameter data via
the optional CAN bus. To do so, the master controller must send a synchronization tele-
gram to the connected inverters at certain intervals. In this way, the inverters synchro-
nize themselves to the master controller. P818 is used for setting the identifier (address)
of the synchronization message in the inverter for the optional CAN bus. Make sure
there is no overlap between the identifiers for the process data or parameter data tele-
grams.
P819 Fieldbus
timeout delay
Setting range: 0 ... 0.5 ... 650 s
P819 is used to set the monitoring time for data transfer via the appropriate fieldbus
(MC_41A
→
PROFIBUS-DP or MCH42A
→
INTERBUS-LWL). If no data traffic takes
place via the fieldbus during the time period set in P819, MOVIDRIVE
®
will execute the
error response set in P831 FIELDBUS TIMEOUT response . When P819 is set to the
value 0 or 650, data transmission via the fieldbus is not monitored. The timeout time is
specified automatically by the DP master with PROFIBUS-DP and DeviceNet. Changing
this parameter does not have any effect and is overwritten whenever the PROFIBUS-
DP is started up again.