System Manual – MOVIDRIVE® compact Drive Inverters
79
2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
Line choke type ND..
Technical Data and Dimension Drawings
2.15
Line choke type ND..
•
To increase overvoltage protection.
•
To limit the charging current when several inverters are connected together in paral-
lel on the input end with shared mains contactors (rated current of line choke = total
of inverter currents).
•
ND.. line filters have cRUus approval independent of the MOVIDRIVE
®
drive invert-
ers.
Dimension draw-
ings for ND...
(1) Space for installation terminals
Input: 1U1, 1V1, 1W1
Output: 1U2, 1V2, 1W2
Any mounting position
Line choke type
ND020-013
ND030-023
1)
ND045-013
ND085-013
ND150-013
ND200-0033
Part number
826 012 5
827 151 8
826 013 3
826 014 1
825 548 2
826 579 8
Rated voltage
U
N
3
×
AC 380 V -10 % ... 3
×
AC 500 V +10 %, 50/60 Hz
Rated current
2)
I
N
AC 20 A
AC 30 A
AC 45 A
AC 85 A
AC 150 A
AC 200 A
Power loss at I
N
P
V
10 W
30 W
15 W
25 W
65 W
100 W
Inductance L
N
0.1 mH
0.2 mH
0.1 mH
0.1 mH
0.1 mH
0.03 mH
Ambient temperature
ϑ
U
–25 °C ... +45 °C
Enclosure
IP 00 (EN 60529)
Connections
Terminal strips
4 mm
2
(AWG12)
Terminal strips
2.5 mm
2
... 10 mm
2
(AWG13 ... AWG8)
Terminal blocks
10 mm
2
(AWG8)
Terminal blocks
35 mm
2
(AWG2)
M10 stud
PI: M8 stud
Tightening torque
0.6 ... 0.8 Nm
max. 2.5 Nm
3.2 ... 3.7 Nm
M10 stud: 10 Nm
PI: 6 Nm
Assignment to AC 400/500 V units (...-5_3)
Rated operation (100 %)
0015...0075
0110...0220
0300...0450
and
MDR60A0370
0550/0750
MDR60A0750
Increased power (125 %)
0015...0075
0110/0150
0220...0370
0450...0750
Assignment to AC 230 V units (...-2_3)
Rated operation (100 %)
0015...0055
-
0075/0110
0150/0220
0300
-
Increased power (125 %)
0015...0037
-
0055/0075
0110/0150
0220/0300
-
1) You can implement ND030-023 for DC link connection without a regenerative power supply unit using connection type A or B (
→
'MOVIDRIVE
®
MDR60A Regenerative Power Supply Unit' system manual)
2) If more than one MOVIDRIVE
®
unit is connected to a line choke, the total value of the rated currents of the connected units must
not exceed the rated current of the line choke.
58699AXX
Figure 20: Dimension drawing for line chokes ND020.. / ND030.. / ND045.. / ND085..
a
c
c
C
A
[1]
[1]
1U1 1U2 1V1 1V2 1W1 1W2
B b
P
i
f
kVA
Hz
n
Summary of Contents for MOVIDRIVE compact MCH41A
Page 2: ...SEW EURODRIVE Driving the world...
Page 432: ......