System Manual – MOVIDRIVE® compact Drive Inverters
10
Startup with the DBG11B keypad
Startup
•
After startup is complete, copy the parameter set from MOVIDRIVE
®
to the DBG11B
keypad (P807 "MDX
→
DBG"). This way, the DBG11B can be used to transfer the
parameter set to other MOVIDRIVE
®
units (P 806 "DBG
→
MDX").
•
Enter parameter settings that differ from the factory setting in the parameter list
(
→
•
In the case of non-SEW motors, set the correct brake application time (P732 / P735).
•
For starting the motor, refer to the "Starting the motor" section (
→
•
With
∆
connection and transition point at 87 Hz
→
set parameter P302
/
312
"Maximum speed 1/2" to the value for 87 Hz.
12. Start the calculation for startup by choosing "YES."
C06*
NO
CALCULATION
FOR SEW MOTORS
13. The calculation is performed.
FOR NON-SEW MOTORS
13. For non-SEW motors, a calibration process is required to
perform the calculation:
•
When prompted, set a "1" signal at terminal DIØØ
"/CONTROL.INHIBIT."
•
Enter a "0" signal at terminal DIØØ "/CONTROLLER
INHIBIT" after the calibration process is complete.
•
If the motor cannot be calibrated (energized), estimate the
motor parameters.
14. The "SAVE" menu command appears automatically. The
keypad is already in edit mode.
C08*
_NO
SAVE
15. Set "SAVE" to "YES". The data (motor parameters) is copied to
the non-volatile memory of MOVIDRIVE
®
.
DATA IS
BEING COPIED...
16. The startup procedure is now complete. Leave the startup
menu by pressing the E or the Q key. The basic display
appears.
CONTROLLER INHIBIT
CURRENT:
0
A