Explanation of the parameters
Parameters
P64x Analog outputs optional
Only with MCF/MCV/MCS40A, not MCH or MCx41A.
P640 / P643 Ana-
log output AO1 /
AO2
Depending on P642 Operating mode AO1 the signal range is 0 (4) ... 20 mA.
The following functions can be assigned to the analog outputs:
P641 Scaling AO1
Setting range: –10 ... 0 ... 1 ... 10
The slope of the characteristic curve for the analog outputs is defined.
Function
Scaling (at P641/P644 = 1)
Explanation
Factory
setting
Reference value
Output value
NO FUNCTION
Always 0 mA
–
RAMP INPUT
+/–3000 1/min
20 mA
Setpoint speed at the input of the internal ramp
generator
SET SPEED
+/–3000 1/min
20 mA
Valid setpoint speed (output ramp generator or cor-
recting variable of master controller)
ACTUAL SPEED
+/–3000 1/min
20 mA
Actual speed
AO1
ACTUAL FRE-
QUENCY
+/–100 Hz
20 mA
Rotating field frequency
OUTPUT CUR-
RENT
150 % I
N
20 mA
Apparent current
ACTIVE CURRENT
+/–150 % I
N
20
mA
Active current, positive when torque is in positive
sense of rotation; negative when torque is in nega-
tive sense of rotation.
RELATIVE
TORQUE
+/–150 % I
N
20 mA
Active current that forms the torque; the value "0" is
always output in VFC operating modes.
UNIT UTILIZATION
150 %
20 mA
Current unit utilization
IPOS OUTPUT
+/–10 000 digits
20 mA
Internal IPOS values (see IPOS
plus®
manual)
IPOS OUTPUT 2
+/–10 000 digits
20 mA
Internal IPOS values (see IPOS
plus®
manual)
05593AEN
Figure 44: Slope of the characteristic curve for the analog outputs
P6..
P60.
P600