192
System Manual – MOVIDRIVE® compact Drive Inverters
4
Motor selection for asynchronous AC motors (VFC)
Project Planning
Motor selection for delta connection (AC 230 V / 50 Hz)
P
max
[kW] for operation on MOVIDRIVE
®
compact
MCF/MCV/MCH 4_A...-2_3 (AC 230 V units)
Connection
∆
/ AC 230 V
Cooling
Own
Forced
f
min
- f
max
[Hz]
10 - 50
6 - 60
5 - 70 / 5.5 - 80
≤
2.5 - 50 /
≤
3 - 60
1)
1) The following applies to MCF, MCV and MCH without speed control: f
min
= 0.5 Hz
n
min
- n
max
[1/min]
300 - 1500
180 - 1800
150 - 2100 / 165 - 2400
≤
75 - 1500 /
≤
90 - 1800
Setting range
1:5
1:10
1:15
≥
1:20
Motor type
2)
2) In load type S3 (40 % cdf), the motor can be operated at its listed power (P = P
n
) without forced cooling. Example: P
stat
= 2 kW,
P
dyn
= 2.5 kW
→
selected motor DV100M4 (P
n
= 2.2 kW).
Rated power P
n
[kW]
P = P
reduced
P = P
n
[kW]
MCF/MCV/MCH
3)
4_A...-2_3
3) The units listed here permit intermittent loads of up to 1.5 times the rated load in the specific application. With variable torque load and
constant load without overload, each inverter can also be operated with increased continuous output power (
→
Sec. Technical Data).
The continuous output current of 125 % of the rated unit current is only available at f
PWM
= 4 kHz.
[kW]
MCF/MCV/MCH
4_A...-2_3
DT71D4
0.37
0.25
0015
0.37
0015
DT80K4
0.55
0.37
0.55
DT80N4
0.75
0.55
0.75
DT90S4
1.1
0.75
1.1
DT90L4
1.5
1.1
1.5
DV100M4
2.2
1.5
2.2
0022
DV100L4
3.0
2.2
0022
3.0
0030
DV112M4
4.0
3.0
0030
4.0
0040
DV132S4
5.5
4.0
0040
5.5
0055
DV132M4
7.5
5.5
0055
7.5
0075
DV132ML4
9.2
7.5
0075
9.2
0110
DV160M4
11
9.2
0110
11
DV160L4
15
11
15
0150
DV180M4
18.5
15
0150
18.5
0220
DV180L4
22
18.5
0220
22
0300
DV200L4
30
22
30
DV225S4
37
30
0300
-
Summary of Contents for MOVIDRIVE compact MCH41A