Connection of motor encoder and external encoder
Installation
Incremental
encoder simula-
tion
You can also use X14 as the output for incremental encoder simulation. To do so, you
have to jumper the "switchover" (X14:4 for MCV/MCS4_A, X14:7 for MCH4_A) with
DGND (X14:5 for MCV/MCS4_A, X14:8 for MCH4_A). X14 then supplies incremental
encoder signals with a signal level in accordance with RS422. The number of pulses is:
•
For MCV4_A as at X15 motor encoder input
•
For MCS4_A 1024 pulses/revolution
•
For MCH4_A with Hiperface encoder 1024 pulses/revolution
•
For MCH4_A with sin/cos encoder or TTL sensor as at X15 Motor encoder input
Connection to
MCV/MCS4_A
Part number of the prefabricated cable:
•
Fixed installation only:
815 354 X
Connection to
MCH4_A
59865AEN
Bild 135: Connecting the incremental encoder simulation to MCV/MCS4_A
1
6
2
7
3
8
9
5
4
YE
GN
RD
BU
PK
GY
WH
BN
VT
5
1
9
6
MOVIDRIVE
X14:
®
max. 100 m
A (K1)
(
)
B (K2)
(
)
C (K0)
(
)
UB
A K1
B K2
C K0
⊥
쵰
쵰
switchover
59870AXX
Figure 136: Connecting the incremental encoder simulation to MCH4_A
1
9
2
10
3
11
15
8
7
쵰
쵰
1
8
9
15
max. 100 m
MOVIDRIVE®
compact
X14:
YE
GN
RD
BU
PK
GY
MCH42A