376
System Manual – MOVIDRIVE® compact Drive Inverters
10
Starting up the inverter with INTERBUS (MCH42A)
Startup
Object "Download
parameter block"
The "Download parameter block" object can be used to write a maximum of 38
MOVIDRIVE
®
drive parameters at the same time with a single write service.
Consequently, this object offers the possibility to set the parameters of the inverter, for
example during the starting phase, with a single call of the write service. Because only
a few parameters generally have to be changed, this parameter block with a maximum
of 38 parameters is sufficient for nearly all applications. The user data area is set to 38
x 6 + 2 Byte = 230 Byte (Type Octet String). The following table shows the structure of
the "Download parameter block" object.
The "download parameter block" object is only handled locally on the INTERBUS
interface and is defined as in the following table.
Octet
Meaning
Note
0
Reserved (0)
1
Number of parameter
1 ... 38 parameter
2
Index high
1. Parameters
3
Index low
4
MSB data
5
Data
6
Data
7
LSB data
8
Index high
...
...
223
LSB data
224
Index high
38. Parameters
225
Index low
226
MSB data
227
Data
228
Data
229
LSB data
Index:
8296
Object code:
7 (simple variable)
Data type index:
10 (octet string)
Length:
230
Local address:
Password:
Access groups:
Access rights:
Write all
Name[16]:
-
Extension length:
-
0
0
I
Summary of Contents for MOVIDRIVE compact MCH41A
Page 2: ...SEW EURODRIVE Driving the world...
Page 432: ......