System Manual – MOVIDRIVE® compact Drive Inverters
255
4
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
Output filter type HF...
Project Planning
The procedure for selecting the PWM frequency and checking the inverter is summa-
rized in the following figure.
60145AEN
Noise-sensitive
environment in which HF is used
(no motor!)
No
Motor cable type
High EMC requirements
Optimized grounded filter
Shielded
w/o U
z
connection:
(P862) PWM frequency 4 / 8 kHz
W. U
z
connection
(P860) PWM frequency 12/16 kHz
(P862) PWM frequency = FIX
Yes
Unshielded
Length of motor cable
(also total length for
group drive)
> 20 m
< 20 m
No
Yes
Mains voltage?
FI output current is increased by
u =
12 %
(12 kHz)
u =
8 %
(16 kHz)
3 x AC 400 V
HF...-403 not permitted
FI output current is increased by
u =
15 %
(12 kHz)
u =
12 %
(16 kHz)
3 x AC 500 V
Select the HF depending on the
motor current
in the table (Sec. "Technical Data and Dimension Drawings - HF.. Output Filter).
Note:
I
HF_rated
I
rated_motor
I
Motor
Length of motor cable only
limited by voltage drop
Length of motor cable only
limited by voltage drop
Required FI output current
= (1+u) x motor current
Take the minimization of the FI output current into account.
Requirements: power reduction through PWM frequency,
ambient temperature, continuous current consumption.
See Sec. "Project Planning" in the MOVIDRIVE compact system manual
FI output current does not
increase (u = 0)
3 x AC 230 V
FI output current is increased by
u =
4 %
(12 kHz)
u =
3 %
(16 kHz)
Is the FI output current sufficient?
Yes
No
Select larger
FI
Checking the frequency inverter (FI)
and selecting the HF filter
Selecting the PWM frequency
and VDClink connection