External DC 24 V voltage supply
Project Planning
4.19
External DC 24 V voltage supply
MOVIDRIVE
®
compact
units have an internal DC 24 V supply with a maximum contin-
uous power of 50 W. The units can be operated without an external DC 24 V voltage
supply. If the inverter’s control electronics are to remain ready for operation when the
power supply is switched off, an external DC 24 V power supply unit with at least 50 W
continuous output power must be connected at VI24. The permitted peak output power
must be at least 100 W for 1 s. This power supply unit then takes over the complete
DC 24 V power supply for MOVIDRIVE
®
compact
. In this case, switch on the external
DC 24 V power supply unit before or at the same time as the mains contactor.
NOTE
SEW-EURODRIVE recommends operating units with fieldbus (MC_41A and
MCH42A) with an external DC 24 V voltage supply.
05305AXX
Figure 90: Connecting an external DC 24 V voltage supply
X10:
MCF/MCV/MCS
MCH
24 V
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
REF1
AI11
REF2
AI12
SC11
AI21
SC12
AGND
DIØØ
DIØ1
DIØ2
DIØ3
DIØ4
DIØ5
DCOM
VO24
DGND
DOØ1-C
DOØ2
DOØ1-NO
DBØØ
DOØ1-NC
DGND
VI24
X12:
24 V
1
2
3
4
5
6
7
DBØØ
DOØ2
VI24
DOØ1-C
DOØ1-NO
DOØ1-NC
DGND