Starting up the inverter with INTERBUS (MCH42A)
Startup
In the "Device Parameterization" window, select "Device / Read Parameter List" from
the menu.
If the device parameters have been read in, project planning of the PCP channel was
performed correctly. The read-in process can be aborted.
If an error message appears instead of the progress indicator, check the PCP configu-
ration and allocation of CRs. If necessary, format the parameterization memory of the
interface module again and then write the new project in the parameterization memory.
Next, perform the parameterization procedure of the interface module again and repeat
this test sequence for checking the PCP connection.
03722AXX
Figure 156: Window for device parameterization using the CMD tool
03723AXX
Figure 157: The CMD tool reads device parameters, i.e. PCP communication is OK.