System Manual – MOVIDRIVE® compact Drive Inverters
31
2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
MOVIDRIVE® compact MC_4_A...-5_3 (AC 400/500 V units)
Technical Data and Dimension Drawings
2.3
MOVIDRIVE
®
compact MC_4_A...-5_3 (AC 400/500 V units)
Size 1
02570AXX
MOVIDRIVE
®
compact
0015-5A3-4-0_
0022-5A3-4-0_
0030-5A3-4-0_
0040-5A3-4-0_
INPUT
Supply voltage
V
mains
3
×
AC 380 V –10 % ... 3
×
AC 500 V +10 %
Supply frequency
f
mains
50 Hz ... 60 Hz
±
5 %
Rated mains current
1)
I
mains
100 %
(when V
mains
= 3
×
AC 400 V) 125%
AC 3.6 A
AC 4.5 A
AC 5.0 A
AC 6.2 A
AC 6.3 A
AC 7.9 A
AC 8.6 A
AC 10.7 A
OUTPUT
Apparent output power
2)
S
N
(when V
mains
= 3
×
AC 400...500 V)
2.8 kVA
3.8 kVA
4.9 kVA
6.6 kVA
Rated output current
1)
I
N
(when V
mains
= 3
×
AC 400 V)
AC 4 A
AC 5.5 A
AC 7 A
AC 9.5 A
Current limitation
I
max
Motor and regenerative 150 % I
N
, duration depending on the capacity utilization
Internal current limitation
I
max
= 0...150 % can be set in menu (P303 / P313)
Minimum permitted braking
R
BRmin
resistance value (4Q operation)
68
Ω
Output voltage
U
A
Max. V
mains
PWM frequency
f
PWM
Following values can be set: 4/8/12/16 kHz
Speed range / resolution
n
A
/
∆
n
A
–5500 ... 0 ... +5500 min
–1
/ 0.2 min
–1
across the entire range
GENERAL INFORMATION
Power loss at P
N
P
Vmax
85 W
105 W
130 W
180 W
Cooling air consumption
40 m
3
/h
Weight
2.8 kg
Dimensions
W
×
H
×
D
MCF/MCV/MCS:
105
×
315
×
155 mm
MCH:
105
×
315
×
161 mm
1) When V
mains
= 3
×
AC 500 V, the mains currents and output currents must be reduced by 20 % compared to the rated data.
2) The power data applies to f
PWM
= 4 kHz (factory setting for VFC operating modes).
P
i
f
kVA
Hz
n