HPV1000-App_Note_02
Closed Loop Start Guide
Guide to set up HPV1000 drive in Closed Loop
Page 1: ...HPV1000 App_Note_02 HPV1000 App_Note_02 Closed Loop Start Guide Guide to set up HPV1000 drive in Closed Loop...
Page 2: ...nufacturers have different interfaces it is recommended that the parameters in the drive be set to what is recommended by the elevator controller in their technical manual Closed Loop Operation Set up...
Page 3: ...parameters CONTRACT CAR SPD A1 parameter should be the lift contract speed in m s This can be verified with a hand tachometer if required and adjusted if required CONTRACT MTR SPD A1 parameter should...
Page 4: ...the U9 menu and enter the following information Tune No Rotate1 TUNING MODE SEL U9 Motor Rated Power in kW MTR RATED POWER U9 Rated Voltage in V RATED VOLTAGE U9 Rated Current in A RATED CURRENT U9 R...
Page 5: ...tment CONTRACT CAR SPD Elevator contract speed 2 0 m s Adjust to speed the installation is rated to run at CONTRACT MTR SPD Motor speed at elevator contract speed 1450 0 rpm Adjust this value to ensur...
Page 6: ...output power 0 kW Set to motor kW rating as per the motor nameplate Should be set in U9 during autotune RATED MTR VOLTS Rated Motor Voltage 0 VAC Set to motor Voltage rating as per the motor nameplate...
Page 7: ...dy roped If the motor is not roped then the Standard Tune method can be used to learn the No Load Current value Note that when performing the autotune the drive will also ask for the following paramet...