HPV1000-App_Note_02
Closed Loop Start Guide
Electrical interference and mechanical speed modulations are common problems that can result in improper
speed feedback getting to the drive. To help avoid these common problems, the following electrical and
mechanical considerations are suggested.
IMPORTANT-
Proper encoder speed feedback is essential for a drive to provide proper motor control.
Electrical Considerations
•
If possible, insulate both the encoder case and shaft from the motor.
•
Use twisted pair cable with shield tied to chassis ground at drive end
•
Use limited slew rate differential line drivers.
•
Do not allow capacitors from internal encoder electronics to case.
•
Do not exceed the operating specification of the encoder/drive.
•
Use the proper encoder supply voltage and use the highest possible voltage available. (i.e. 12V
DC
is
preferred because less susceptible to noise)
Mechanical Considerations
•
Use direct motor mounting without couplings where possible.
•
Use hub or hollow shaft encoder with concentric motor stub shaft.
•
If possible, use a mechanical protective cover for exposed encoders.
Autotune
7) The autotune can now be performed by navigating to the U9 menu. The drive has several options for
autotuning the motor, however usually the motor will be roped, and so the
‘Tune-No Rotate1’ (Static) method
will be used.
If the ropes are off, and the motor can turn freely, the ‘Standard Tune’ (Rotating) method can be used.
Navigate to the U9 menu and enter the following information:
•
‘Tune-No Rotate1’ (TUNING MODE SEL(U9))
•
Motor Rated Power in kW (MTR RATED POWER(U9))
•
Rated Voltage in V (RATED VOLTAGE(U9))
•
Rated Current in A (RATED CURRENT(U9))
•
Rated Frequency in Hz (RATED FREQUENCY (U9))
•
Number of Poles (NUMBER OF POLES(U9))
•
Rated Motor Speed* (RATED SPEED (U9)) -
This is after slip, so NOT synchronous speed.
•
Encoder Pulses (ENCODER PPR (U9))
•
No Load Current (NO-LOAD CURRENT(U9) -
Enter 35% of the RATED MOTOR CURRENT entered
above for 4 pole motors or 45% for a 6 pole motor
*Note
The rated motor rpm entered must
equal what it can achieve at rated frequency,
at full load and full speed. If synchronous
speed is given on the dataplate, a lower RPM
must be entered. Table 2 gives an indication
of typical motor rated rpm for lift applications.
Once the above information has been entered and the bottom of the menu is reached the screen will display:
‘Auto-tuning. Waiting for command – Tune Ready? Give Run/Hit Enter’.
At this point
DO NOT
press any keypad buttons.
Using your inspection controls,
PRESS AND HOLD
the buttons to run the lift in the
UP DIRECTION
(the lift
will not move, however the tune will begin) If the drive has control of the motor contactors they will now pull in
and the tune will begin.
During this process the drive will display motor speed and motor current for reference.
Once complete the drive will display “END Tune Successful”. The test run UP button can now be released.
Synchronous
speed (50hz)
Rated motor
Speed (rpm)
Number of
motor poles
Typical No
Load Current
1500
1480 - 1340
4
35%
1000
980 - 840
6
45%
Table 2: Synchronous/Asynchronous Motor Speeds &
Motor Poles Reference for 50Hz