7-10
Issue 1.0
March 2001
365-575-389
Installation Manual
Powering
Fuse Insertion
Procedures
The following procedures are used to determine the value of the fuse and its
placement:
(Continued on next page)
Step
Action
Reference
1
Insert 20-amp fuses into the WaveStar OLS 40G or OT
power feeds at the BDFB. If breakers are being used,
put them in the ON position.
2
For Rack and Stack configurations, insert one 10-amp
fuse in each of the designated A and B fuse positions,
for each shelf in the bay, in the fuse panel located in Bay
2 or Bay 4.
Chapter 3,
Equipment
Installation
3
Using the voltmeter, measure the voltage from the top
terminal of each fuse holder on each shelf to the terminal
grounding cable.
Requirement: The voltage should be –48 volts
(between –41.75 and –60.0 VDC) at each fuse holder.
For OLS, see
Figure 7-1.
For OT, see
Figure 7-2.
4
Insert two 10-amp fuses into the fuse holders of the
lower shelf per the following:
a.
Open the retainer from the bottom edge and
swing it up and out of the way.
b.
Put the fuse in the fuse cap, and the entire
assembly in the fuse position on the bay. Be sure
to put the lettering right-side-up.
c.
Push up and in gently on the bottom edge of the
fuse. The fuse will secure in place.
d.
Close the retainer over the fuse cap and snap it in
place.
Requirement: The PWR ON LED is illuminated on the
indicator strip for the lower shelf.
Summary of Contents for WaveStar OLS 40G
Page 4: ......
Page 12: ...Contents xii Issue 1 0 March 2001 365 575 389 Installation Manual...
Page 24: ...Tables xxiv Issue 1 0 March 2001 365 575 389 Installation Manual...
Page 126: ...3 50 Issue 1 0 March 2001 365 575 389 Installation Manual Equipment Installation...
Page 156: ...4 30 Issue 1 0 March 2001 365 575 389 Installation Manual Power Cable Installation...
Page 228: ...5 72 Issue 1 0 March 2001 365 575 389 Installation Manual Wired Cable Installation...
Page 366: ...7 16 Issue 1 0 March 2001 365 575 389 Installation Manual Powering...
Page 436: ...9 46 Issue 1 0 March 2001 365 575 389 Installation Manual Local Installation Testing...
Page 487: ...Issue 1 0 March 2001 12 15 12 Troubleshooting 12 Contents Background 2 Troubleshooting Table 3...
Page 500: ...12 28 Issue 1 0 March 2001 365 575 389 Installation Manual Troubleshooting...
Page 501: ...Issue 1 0 March 2001 A 1 A Releases 1 0 and2 0LBO Selection Tables A Contents Overview 2...
Page 571: ...Issue 1 0 March 2001 H 1 H Optical Protection Switch OPS H Contents Overview 2...