7-36
Setting
value
Page
Control mode
Function
Setting
value
Page
Flux
vector
Open loop
Vector
V/f
w/PG
V/f
Function
2
Option/Inverter selection (ON: Option)
OK
OK
OK
OK
6-79
3
Multi-step speed reference 1
When H3-05 is set to “0,” this function is
combined with “Main/auxiliary speed switch.”
OK
OK
OK
OK
5-17
4
Multi-step speed reference 2
OK
OK
OK
OK
5-17
5
Multi-step speed reference 3
OK
OK
OK
OK
5-17
6
Jog frequency reference (has priority over
multi-step speed)
OK
OK
OK
OK
5-17
7
Multi-accel/decel time 1
OK
OK
OK
OK
5-18
8
Baseblock NO (contact a: Base block ON)
OK
OK
OK
OK
6-80
9
Baseblock NC (contact b: Base block OFF)
OK
OK
OK
OK
6-80
A
Accel/decel ramp hold (ON: Accel/decel stopped,
frequency on hold)
OK
OK
OK
OK
6-80
B
OH2 alarm signal input (ON: OH2 will be
displayed)
OK
OK
OK
OK
6-81
C
Multi-function analog input selection (ON: Enable)
OK
OK
OK
OK
6-81
D
V/f mode selection (ON: Speed feedback control
disabled, (normal V/f control))
---
OK
---
---
6-82
E
Speed control integral reset (ON: Integral control
disabled)
---
OK
---
OK
6-82
F
Not used: Do not set
---
---
---
---
---
10
UP command “MOP Increase” (Always set with
the DOWN command)
OK
OK
OK
OK
6-82
11
DOWN command “MOP Decrease” (Always set
with the UP command)
OK
OK
OK
OK
6-82
12
FJOG command (ON: Forward rotation for jog
frequency d1-09)
OK
OK
OK
OK
5-19
13
RJOG command (ON: Reverse rotation for jog
frequency d1-09)
OK
OK
OK
OK
5-19
14
Fault reset (Reset when turned ON)
OK
OK
OK
OK
6-83
15
Emergency stop “Fast-stop” (Normally open
condition, When ON: Decelerate to a stop in the
emergency stop time set in c1-09)
OK
OK
OK
OK
5-19
16
Motor 2 selection: Selection of motor 1 or motor 2
for two-motor switching control (ON: Motor 2
selected)
OK
OK
OK
OK
---
17
Emergency stop N.C. (ON: Decelerate to a stop in
the emergency stop time set in c1-09)
OK
OK
OK
OK
5-19
18
Timer function input (Functions are set with
b4-01, b4-02 and the timer function is set at the
same time)
OK
OK
OK
OK
6-46
19
PID control ON/OFF (ON: PID control disabled)
OK
OK
OK
OK
6-84
1A
Multi-accel/decel time 2
OK
OK
OK
OK
5-18
1B
Parameter write access (ON: Parameters can be
overwritten; OFF: All parameters other than
frequency monitor are write protected.)
OK
OK
OK
OK
6-84
1C
Trim control increase (ON: d4-02 frequencies are
added to analog frequency references.)
OK
OK
OK
OK
6-84
Parameter Lists
Chapter 7
Summary of Contents for SYSDRIVE 3G3FV
Page 1: ...USER S MANUAL High function General purpose Inverter SYSDRIVE 3G3FV Cat No I516 E1 4 ...
Page 16: ...Chapter 1 Introduction 1 1 Function 1 2 Nomenclature 1 3 New Functions 1 ...
Page 33: ...Chapter 2 Installation 2 1 Mounting 2 2 Wiring 2 ...
Page 112: ...Chapter 4 Trial Operation 4 1 Procedure 4 2 Operation Example 4 ...
Page 289: ...Chapter 7 Parameter Lists 7 1 Initialize Mode Parameters 7 2 Program Mode Parameter List 7 ...
Page 366: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9 ...
Page 395: ...Chapter 10 Appendix 10 1 Notes on Using the Inverter for a Motor 10 ...