7-38
D
Digital Outputs List
Setting
l
Control mode
Page
g
value
V/f
V/f
w/PG
Open loop
Vector
Flux
vector
g
0
During run 1
OK
OK
OK
OK
6-92
1
Excitation
OK
OK
OK
OK
6-92
2
Frequency (ref/out) agree 1: detection width
L4-02
OK
OK
OK
OK
6-104
3
Desired frequency (ref/setting) agree 1 (ON:
Output frequency =
±
L4-01, detection width
L4-02)
OK
OK
OK
OK
6-104
4
Frequency detection 1 (ON: +L4-01
+
output
frequency
+
–L4-01, detection width L4-02)
OK
OK
OK
OK
6-104
5
Frequency detection 2
(ON: Output frequency
+
+L4-01 or output
frequency
)
–L4-01, detection width L4-02)
OK
OK
OK
OK
6-104
6
Inverter operation ready
READY: After initialization, no faults
OK
OK
OK
OK
---
7
During DC bus low voltage (UV) detection
OK
OK
OK
OK
---
8
During baseblock 1 (ON: during baseblock)
OK
OK
OK
OK
---
9
Operation reference (ON: Operator)
OK
OK
OK
OK
---
A
Run command remote operation (ON: Operator)
OK
OK
OK
OK
---
B
Overtorque detection 1 NO (contact a: ON,
overtorque detection)
OK
OK
OK
OK
6-108
C
Loss of frequency reference (Effective when
operation selection is “1” for L4-05 frequency
reference missing)
OK
OK
OK
OK
6-105
D
DB overheat (ON: Resistance overheat or braking
Tr fault)
OK
OK
OK
OK
---
E
Fault (ON: Faults other than CPF00, CPF01 have
occurred.)
OK
OK
OK
OK
8-1
F
Not used. Do not set.
---
---
---
---
---
10
Minor fault (ON:Report displayed)
OK
OK
OK
OK
8-8
11
Fault reset command active
OK
OK
OK
OK
---
12
Timer output
OK
OK
OK
OK
6-46
13
Frequency (ref/out) agree 2 (Detection width:
L4-04)
OK
OK
OK
OK
6-104
14
Desired frequency (ref/setting) agree 2 (ON:
Output frequency = L4-03, detection width L4-04)
OK
OK
OK
OK
6-104
15
Frequency detection 3 (ON: output frequency
)
–L4-03, detection width L4-04)
OK
OK
OK
OK
6-104
16
Frequency detection 4 (ON: output frequency
+
–L4-03, detection width L4-04)
OK
OK
OK
OK
6-104
17
Overtorque detection 1 NC (Contact b: OFF,
torque detection)
OK
OK
OK
OK
6-108
18
Overtorque detection 2 NO (Contact a: ON,
torque detection)
OK
OK
OK
OK
6-108
19
Overtorque detection 2 NC (Contact b: OFF,
torque detection)
OK
OK
OK
OK
6-108
1A
During reverse run (ON: during reverse run)
OK
OK
OK
OK
---
Parameter Lists
Chapter 7
Summary of Contents for SYSDRIVE 3G3FV
Page 1: ...USER S MANUAL High function General purpose Inverter SYSDRIVE 3G3FV Cat No I516 E1 4 ...
Page 16: ...Chapter 1 Introduction 1 1 Function 1 2 Nomenclature 1 3 New Functions 1 ...
Page 33: ...Chapter 2 Installation 2 1 Mounting 2 2 Wiring 2 ...
Page 112: ...Chapter 4 Trial Operation 4 1 Procedure 4 2 Operation Example 4 ...
Page 289: ...Chapter 7 Parameter Lists 7 1 Initialize Mode Parameters 7 2 Program Mode Parameter List 7 ...
Page 366: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9 ...
Page 395: ...Chapter 10 Appendix 10 1 Notes on Using the Inverter for a Motor 10 ...