6-113
Setting
Function
0
No change. (Retain current settings.)
1
Record user defaults. (Record the current parameter settings as user defaults.)
2
Clear user defaults. (Clear the recorded user defaults.)
Parameter
Display name
Setting
Units
Default
Valid access levels
number
p y
g
range
setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
o2-04
Inverter Model #
0 to FF
---
0
Basic or Advanced
•
Do not change this parameter setting; it is used by the manufacturer to identify the Inverter model.
•
The setting range and default setting depend on the Inverter capacity. The settings shown in the table
are for a 200-V class, 0.4 kW Inverter.
Parameter
Display name
Setting
Units
Default
Valid access levels
number
p y
g
range
setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
o2-05
Operator M.O.P.
0, 1
---
0
Advanced
•
This parameter determines whether it is necessary to press the Enter Key when changing the frequen-
cy reference with the Digital Operator’s frequency reference monitor; it cannot be changed during op-
eration.
•
When o2-05 is set to 1 (Enter Key input not required.), the frequency reference changes simulta-
neously with the Digital Operator’s value.
Setting
Function
0
Enter Key input required.
1
Enter Key input not required.
Parameter
Display name
Setting
Units
Default
Valid access levels
number
p y
g
range
setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
o2-06
Oper Detection
0 or 1
---
0
Advanced
•
This parameter specifies whether to stop operation when the Digital Operator is disconnected; it can-
not be changed during operation.
Setting
Function
0
Disable Operator detection. (Continue operation when the Digital Operator is disconnected.)
1
Enable Operator detection. (Detect an OPR fault when the Digital Operator is disconnected, stop
the Inverter output, and operate the fault contact.)
Parameter
Display name
Setting
Units
Default
Valid access levels
number
p y
g
range
setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
o2-07
Elapsed Time Set
0 to 65535
h
0
Advanced
o2-08
Elapsed Time Run
0 or 1
---
0
Advanced
Note These parameters cannot be changed during operation
•
Set the initial elapsed time in parameter o2-07. The elapsed operating time will start from this value.
Note When parameter o2-07 is set to the initial elapsed time, the accumulated operating time will be the
same as the value set in the parameter U1-13.
Advanced Operation
Chapter 6
Summary of Contents for SYSDRIVE 3G3FV
Page 1: ...USER S MANUAL High function General purpose Inverter SYSDRIVE 3G3FV Cat No I516 E1 4 ...
Page 16: ...Chapter 1 Introduction 1 1 Function 1 2 Nomenclature 1 3 New Functions 1 ...
Page 33: ...Chapter 2 Installation 2 1 Mounting 2 2 Wiring 2 ...
Page 112: ...Chapter 4 Trial Operation 4 1 Procedure 4 2 Operation Example 4 ...
Page 289: ...Chapter 7 Parameter Lists 7 1 Initialize Mode Parameters 7 2 Program Mode Parameter List 7 ...
Page 366: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9 ...
Page 395: ...Chapter 10 Appendix 10 1 Notes on Using the Inverter for a Motor 10 ...