2-17
Symbol
Signal level
Function
Name
Input
15
Frequency reference power supply
(15 VDC)
15-VDC power supply for frequency refer-
ence.
15 VDC
(
±
10%), 20 mA
max.
33
Frequency reference power supply
(–15 VDC)
–15-VDC power supply for frequency refer-
ence.
–15 VDC
(
±
10%), 20 mA
max.
13
Frequency reference input (voltage)
Frequency reference voltage input terminal
Either 0 to +10 V or 0 to
±
10 V can be se-
lected as the parameter (H3-01).
0 to 10 VDC (In-
put impedance:
20 k
Ω
)
0 to
±
10 V (In-
put impedance:
20 k
Ω
)
14
Frequency reference input (current)
Current input terminal for frequency refer-
ence.
4 to 20 mA (In-
put impedance:
250 k
Ω
)
16
Multi-function analog input
Set by parameter H3-05.
0 to 10 VDC (In-
put impedance:
20 k
Ω
)
0 to
±
10 V (In-
put impedance:
20 k
Ω
)
17
Frequency reference input common
Common for analog input signal.
---
12
Shielded wire connection ground
Shielded terminal for sequence input, fre-
quency reference input.
---
Output
9
Multi-function contact output
Set by parameter H2-01 (during running).
Contact output
(SPST-NO)
30 VDC, 1 A
10
Multi-function contact output common
30 VDC, 1 A
max.
250 VAC, 1 A
max.
25
Multi-function output 1
Set by parameter H2-02 (zero speed
detection).
Open collector
output
48 V 50
A
26
Multi-function output 2
Set by parameter H2-03 (agree output ref-
erence detection).
48 V, 50 mA
max.
27
Multi-function output 1 and 2 common
Common for terminals, 25, 26.
18
Fault output (NO condition)
When fault occurs:
Terminals 18 to 20: Closed
Contact output
(SPDT)
19
Fault output (NC condition)
Terminals 18 to 20: Closed
Terminals 19 to 20: Open
(SPDT)
30 VDC, 1 A
max.
20
Fault output common
max.
250 VAC, 1 A
max.
Output
21
Multi-function analog output 1
Set by parameter H4-01. (Output frequen-
cy: 0 to
±
10 V/
±
100% frequency)
0 to
±
10 VDC
(
±
5%), 0 to
10 VDC (
±
5%)
23
Multi-function analog output 2
Set by parameter H4-01. (Output current:
5 V/Inverter rated current)
(
),
10 VDC (
±
5%),
2 mA max.
22
Multi-function analog output common
Common for analog output.
Note The settings shown in parentheses in the “Function” column for multi-function inputs 1 to 6, multi-
function contact outputs, and multi-function outputs 1 and 2 indicate default settings.
Installation
Chapter 2
Summary of Contents for SYSDRIVE 3G3FV
Page 1: ...USER S MANUAL High function General purpose Inverter SYSDRIVE 3G3FV Cat No I516 E1 4 ...
Page 16: ...Chapter 1 Introduction 1 1 Function 1 2 Nomenclature 1 3 New Functions 1 ...
Page 33: ...Chapter 2 Installation 2 1 Mounting 2 2 Wiring 2 ...
Page 112: ...Chapter 4 Trial Operation 4 1 Procedure 4 2 Operation Example 4 ...
Page 289: ...Chapter 7 Parameter Lists 7 1 Initialize Mode Parameters 7 2 Program Mode Parameter List 7 ...
Page 366: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9 ...
Page 395: ...Chapter 10 Appendix 10 1 Notes on Using the Inverter for a Motor 10 ...